HD45 / HD46
- 19 -
V2.4
7.
Relay activates above threshold A with hysteresis
The contact closes when the measuring value rises above threshold
A
value. The
contact opens if the measuring value falls below the threshold minus the
hysteresis (
A-H
).
8.
Relay activates above threshold A and below threshold B with hysteresis
Relay action is different depending if threshold
A
value is greater or lower than
threshold
B
value.
If threshold
A
value is greater than threshold
B
value, the contact is closed if the
measuring value rises above threshold
A
value or falls below threshold
B
value.
The contact is open if the measuring value is within the interval ranging between
threshold B plus the hysteresis (
B+H
) and threshold
A
minus the hysteresis
(
A-H
).