57
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
10. Settings
EN
10.9.3 Active Power by Frequency P(f)
Menu
512 Power/Frequency
Description
Allows the statistics to be reset. The currency and credit per kWh
can also be configured.
This function alters the fed active power depending on the grid
frequency. If a starting frequency is exceeded, the fed active power
is limited. If a stopping frequency is exceeded, the active power is
no longer fed.
Behavior as per VDE AR N 4105 is described below.
Variant 1
: The grid frequency alters between f
Start
and f
Stop
.
Pm
f (Hz)
fstart
fstop
Gradient (%/Hz)
Fig. 10.1:
Function P(f), variant 1
Once the grid frequency exceeds the value f
Start
, the value of the
active power P
m
being fed at this moment is automatically saved
and active power limiting is activated.
As long as the grid frequency stays above f
Start
and under f
Stop
, the
fed active power value runs along the gradients: Active power drops
with increasing grid frequency and increases with decreasing grid
frequency.
Variant 2
: The grid frequency exceeds f
Stop
.
Pm
f (Hz)
fstart
fstop
Gradient (%/Hz)
Fig. 10.2:
Function P(f), variant 2
When the grid frequency exceeds f
Start
but then remains under f
Stop
,
the solar inverter behaves as described in variant 1.
However, as soon as the grid frequency exceeds f
Stop
, the active
power feed is stopped.
Active power feed will resume once the grid frequency falls below
f
Start
. Once resumed, the active power will increase by 10% per
minute.
Accessing the Menu
Main Menu > User Settings > Active PwCtrl > Power vs freq
➔
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select
User
Settings
and then press the
button.
for assistance.
Ask your installer
energy production.
Changes could affect
2. Press the button to confirm.
➔
Reactive PwCtrl
Active PwCtrl
-------------------
500
User settings
3. Press the
buttons to
select
Active PwCtrl
and then
press the button.
➔
-------------------
Power vs freq
Power reduction
-------------------
510 Active PwCtrl
4. Press the
buttons to
select
Power vs freq
and then
press the button.
➔
Stop freq: 51.50Hz
Start freq: 50.20Hz
-------------------
512 Power vs freq
5. Select a parameter with the
buttons. Press the but-
ton to change the value.
Configurable Parameters
Display Text
Designation
Description
Start freq
Start frequency
Frequency at which the
feeding of active power is
limited.
Value range: 50.00
- 65.00 Hz
Standard: 50.20 Hz
Stop freq
Stop frequency
Frequency at which the
feeding of active power is
stopped.
Value range: 50.00
- 65.00 Hz
Standard: 51.50 Hz
Gradient
Gradient
Adjustment of the fed
active power in percent
per Hz.
Value range: 0 - 150 %
Standard: 40 %