Delta Elektronika SM120-25D Скачать руководство пользователя страница 16

SM3000

OPERATING - TROUBLE SHOOTING - CALIBRATING

rev. February 2018

DELTA ELEKTRONIKA B.V.

Page 4 - 5

OPERATING AND STORAGE CONDITIONS

1)

TEM PER A TURE

The op er at ing tem per a ture range at full load is –20 to +50 °C.
But this tem per a ture range only holds when the AIR-IN TAKE and
AIR-OUT 

LET are un 

ob 

structed and the tem 

per 

ture of the

AIR-IN TAKE is not higher than +50 °C.

Please note: a lower tem 

per 

ture ex tends the life of the

power sup ply.

When the power sup ply is 

mounted in a cab i net

 please note that

the tem per a ture of the AIR-INTAKE should be kept low and avoid
a short cir cuit in the air flow i.e. the hot air leav ing the AIR-OUTLET 
en ter ing the AIR-INTAKE again.

The stor age tem per a ture range is –40 to +85 °C.

2)

HU MID ITY

Dur ing nor mal op er a tion hu mid ity will not harm the power sup ply,
pro vided the air is not ag gres sive. The heat nor mally pro duced in
the power sup ply will keep it dry.

Con den sa tion.

Avoid con den sa tion in side the power sup ply, break-down could
be the re sult.
Con den sa tion can oc cur dur ing a pe riod the power sup ply is
switched off (or op er at ing at no load) and the am bi ent tem per a ture 
is  in creas ing  .
Al ways al low the power sup ply to dry be fore switch ing it on again. 

3)

GAL VANIC  IN DUS TRY

For us ing the power sup plies in the gal vanic in dus try it is strongly
rec om mended  to  take  pre cau tions  against  an  ag gres sive  en vi ron -
ment.

An ag gres sive en vi ron ment with acid, salt, etc. can harm the elec -
tronic com po nents. Some times even the cop per traces of the
pc-boards dis solve.

To avoid prob lems the power sup plies should be mounted in a rel -
a tive clean room, or mounted in a cab i net re ceiv ing clean air with
over pres sure. Or a cab i net with a heat exchanger.
 

MAINTENANCE

1)

GEN ERAL

The SM-series power sup plies nor mally need no main te nance or
cal i bra tion. Only care must be taken that the cool ing of the unit is
not ob structed.

2)

COOLING FAN

The built up of dust on the im pel ler of the fan and the heat sink fins
de pends on the en vi ron ment. Since the fan has over-capacity
dust will not pres ent a prob lem very quickly.

The in ter nal con struc tion of the power sup ply is such that no dust
will reach the sen si tive con trol cir cuitry, only the heat sinks in a
tun nel will be cooled by forced air (see fig. 4 - 15).

The ther mal pro tec tion will shut down the out put in case of over -
heat ing, so no dam age will be done to the power sup ply.

It is ad vis able to in spect the fan and the heat sinks reg u larly.

fig. 4 - 15

The fan blows through an in ter nal tun nel,

where the heatsinks are sit u ated

Содержание SM120-25D

Страница 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Страница 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Страница 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Страница 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Страница 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Страница 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Страница 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Страница 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Страница 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Страница 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Страница 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Страница 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Страница 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Страница 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Страница 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Страница 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Страница 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Страница 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Страница 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Страница 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Отзывы: