When the OVP sta tus out put is used as an in di ca tion for ac ci den tal in ter -
rup tion of leads, a de fect in the power sup ply etc., it is rec om mended to set
the limit well above the work ing out put volt age to avoid ac ci den tal lim it ing. 
The  rec om mended  OVP set volt ages can be read from the fol low ing ta ble:

SM

 

15-200

 

D SM

 

30-100

 

D

SM

 

45-70

 

D

SM

 

70-45

 

D

SM

 

120-25

 

D SM

 

300-10

 

D

Vovp

set

Vout + 2 V

Vout + 3 V

Vout + 5 V

Vout + 5 V

Vout + 10 V

Vout + 25 V

Ex am ple: For a SM30-100D set at 24 V out put volt age it is rec om mended to 
set the OVP on 24 + 3 = 27 V.

31)

PO TEN TI OM E TERS

°

Stan dard:

-

CV and CC po ten ti om eters with knobs at front panel,
OVP  po ten ti om e ter  with  screw driver  ad just ment  at
the front panel.

°

Op tion  P001:

-

Screw driver ad just ment for CV, CC and OVP at the
front panel (see fig. 3 - 25).

°

Op tion  P002:

-

Screw driver ad just ment for CV, CC and OVP at the
rear panel (no po ten ti om eters at front panel),
(see fig. 3 - 26).

32)

COOLING

A low noise blower cools the unit. The speed of the fan de pends on the tem -
per a ture of the in ter nal heatsink. At room tem per a ture and full load the fan
will run at a very low speed. The fan does not op er ate on no load. Normally
at 50 °C am bi ent and full load the fan will not work at full speed. Since the
fan is over-rated it will still have enough ca pac ity to cool the unit when dust
par tially ob structs the fins of the heatsinks.
A spe cial fea ture is that the fan blows through a tun nel where the heatsinks
are sit u ated, the del i cate con trol cir cuitry is sep a rated and will not be in the
air flow path (see fig. 3 - 27).
Be cause the air en ters at the left and ex its at the right side it is pos si ble to
stack the power sup plies, no dis tance be tween the units is re quired. Only
the ven ti la tion open ings at the left and right side should be free.

For long life

 the tem per a ture of the air en ter ing on the left side, should be

be low  35 

°

C un der nor mal con di tions. Un der ex treme conditions it should

be be low 50 

°

C.

Note:

 The con trol cir cuit makes the fan start in a pul sat ing mode, dur ing

which pe riod it nor mally pro duces a high pitched sound. This is nor mal.

33)

DI MEN SIONS

fig.  3 - 24

Re mote sens ing, volt age drop in load

leads sub tracts from max. out put

fig. 3 - 25

Screw driver ad just ment at front panel

fig. 3 - 26

Screw driver ad just ment at rear panel

fig. 3 - 27

The fan blows through a tun nel,

where the heatsinks are sit u ated

Содержание SM120-25D

Страница 1: ...rlands www DeltaPowerSupplies com Tel 31 111 413656 SM3000 series PRODUCT MANUAL Contents 1 Datasheet 2 Safety Instructions 3 Descriptions 4 Operating Trouble Shooting Calibration 5 EC Declaration of...

Страница 2: ...ution 3 When programming a high voltage unit directly via a PC or via a network connection either ground the negative power output or use a safety isolated interface For more information and schematic...

Страница 3: ...d separately to recycle it responsibly to promote the sustainable reuse of material resources 11 Removal of safety covers Safety cover s are used to cover potentially hazardous voltages Observe the fo...

Страница 4: ...2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 90 of t...

Страница 5: ...programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that the analog inputs and outputs ar...

Страница 6: ...gh 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Страница 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Страница 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Страница 9: ...recommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fe...

Страница 10: ...ure and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it wil...

Страница 11: ...ITER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating swit...

Страница 12: ...mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage sour...

Страница 13: ...erminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set at t...

Страница 14: ...ended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power connecti...

Страница 15: ...ON For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units in ser...

Страница 16: ...ly to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment An ag...

Страница 17: ...nt is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programming can...

Страница 18: ...ry to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a short SM...

Страница 19: ...h exactly 5 00 V Set output voltage to a low value ensuring the power supply is in CC mode Measure the output current with an accurate shunt Cali brate the current with R686 exactly on the rated max c...

Страница 20: ...al EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage fluctuation and flicker EN 61000 6 1 Generic Immunity residential light industrial EN 61000 6 2 Generic Immunity industrial environment...

Отзывы: