Chapter 4 Parameters
|
|
|
|
4-68
Revision 2016/03, 6ELE, V1.14
Factory Setting: 1
Settings
0
Disable
1
Speed search starts with last frequency command
2
Speed search starts with minimum output frequency (Pr.01.05)
This parameter determines the AC motor drive restart method after External Base Block is enabled.
Output frequency
(H)
Output voltage(V)
08.08 Current Limit
for Speed SearchSpeed
FWD Run
Time
B.B.
Fig 1:B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current Attains Speed Search Level)
A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Speed Search
Synchronization speed detection
Time
B.B.
Fig 2: B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current doesn't Attain Speed Search Level)
A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Speed Search
Synchronization speed detection
Output frequency
(H)
08.08 Current Limit
for Speed SearchSpeed
FWD Run
Time
B.B.
Fig3: B.B. Speed Search with Minimum Output Frequency Upward Timing Chart
A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Restart
Synchronization speed detection
Keep accelerating
A
Output frequency
(H)
06.01
Over current
stall prevention
during acceleration
FWD Run
08.07
Baseblock Time for Speed Search (BB)
Unit: 0.1
Settings
0.1 to 5.0 sec
Factory Setting: 0.5
When momentary power loss is detected, the AC motor drive will block its output and then wait for a specified
period of time (determined by Pr.08.07, called Base-Block Time) before resuming operation. This parameter
should be set at a value to ensure that any residual regeneration voltage from the motor on the output has
disappeared before the drive is activated again.
This parameter also determines the waiting time before resuming operation after External Baseblock and Auto
Restart after Fault (Pr.08.15).
Содержание VFD-EL series
Страница 6: ...This page intentionally left blank ...
Страница 7: ......
Страница 16: ...Revision 2016 03 6ELE V1 14 2 3 ...
Страница 25: ......
Страница 151: ......
Страница 157: ...Revision 2016 03 6ELE V1 14 B 4 Order P N BR1K0W050 Order P N BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040 ...
Страница 181: ...Appendix C How to Select the Right AC Motor Drive Revision 2016 03 6ELE V1 14 C 6 This page intentionally left blank ...