Revision 2016/03, 6ELE, V1.14
4-31
01.00
01.09
01.11
01.10
01.12
Frequency
Time
Accel. Time
Decel. Time
The definition of
Accel./Decel. Time
Max. output
Frequency
setting
operation
frequency
Min. output
frequency
01.05
Resulting
Resulting
Accel. Time
Decel. Time
Resulting Accel./Decel. Time
0 Hz
01.13
Jog Acceleration Time
Unit: 0.1/0.01
Settings
0.1 to 600.0/0.01 to 600.0 sec
Factory Setting: 1.0
01.14
Jog Deceleration Time
Unit: 0.1/0.01
Settings
0.1 to 600.0/0.01 to 600.0 sec
Factory Setting: 1.0
01.15
Jog Frequency
Unit: 0.01
Settings
0.10 to Fmax (Pr.01.00)Hz
Factory Setting: 6.00
Only external terminal JOG (MI3 to MI12) can be used. When the Jog command is “ON”, the AC motor drive
will accelerate from Minimum Output Frequency (Pr.01.05) to Jog Frequency (Pr.01.15). When the Jog
command is “OFF”, the AC motor drive will decelerate from Jog Frequency to zero. The used Accel/Decel
time is set by the Jog Accel/Decel time (Pr.01.13, Pr.01.14).
Before using the JOG command, the drive must be stopped first. And during Jog operation, other operation
commands are not accepted, except FORWARD/REVERSE commands.
01.13
01.12
01.21
Frequency
Time
JOG Accel. Time
JOG Decel. Time
The definition of JOG Accel./Decel. Time
01.15
JOG
Frequency
Min. output
frequency
01.05
0 Hz
01.14
Содержание VFD-EL series
Страница 6: ...This page intentionally left blank ...
Страница 7: ......
Страница 16: ...Revision 2016 03 6ELE V1 14 2 3 ...
Страница 25: ......
Страница 151: ......
Страница 157: ...Revision 2016 03 6ELE V1 14 B 4 Order P N BR1K0W050 Order P N BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040 ...
Страница 181: ...Appendix C How to Select the Right AC Motor Drive Revision 2016 03 6ELE V1 14 C 6 This page intentionally left blank ...