Chapter 4 Parameters
|
|
|
|
4-4
Revision 2016/03, 6ELE, V1.14
Group 1 Basic Parameters
Parameter
Function
Setting
Factory
Setting
Customer
01.00
Maximum Output Frequency (Fmax)
50.00 to
599.0
Hz
60.00
01.01
Maximum Voltage Frequency (Fbase)
0.10 to
599.0
Hz
60.00
01.02
Maximum Output Voltage (Vmax)
115V/230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01.03
Mid-Point Frequency (Fmid)
0.10 to
599.0
Hz
1.50
01.04
Mid-Point Voltage (Vmid)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.05
Minimum Output Frequency (Fmin)
0.10 to
599.0
Hz
1.50
01.06
Minimum Output Voltage (Vmin)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.07
Output Frequency Upper Limit
0.1 to 120.0%
110.0
01.08
Output Frequency Lower Limit
0.0 to100.0 %
0.0
01.09
Accel Time 1
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.10
Decel Time 1
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.11
Accel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.12
Decel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.13
Jog Acceleration Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.14
Jog Deceleration Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.15
Jog Frequency
0.10 Hz to Fmax (Pr.01.00) Hz
6.00
01.16
Auto acceleration / deceleration (refer to
Accel/Decel time setting)
0: Linear Accel/Decel
0
1: Auto Accel, Linear Decel
2: Linear Accel, Auto Decel
3: Auto Accel/Decel (Set by load)
4: Auto Accel/Decel (set by
Accel/Decel Time setting)
01.17
Acceleration S-Curve
0.0 to 10.0 / 0.00 to 10.00 sec
0.0
01.18
Deceleration S-Curve
0.0 to 10.0 / 0.00 to 10.00 sec
0.0
01.19
Accel/Decel Time Unit
0: Unit: 0.1 sec
0
1: Unit: 0.01 sec
01.20
Simple Positioning Stop Frequency 0
0.00~
599.0
Hz
0.00
01.21
Simple Positioning Stop Frequency 1
5.00
01.22
Simple Positioning Stop Frequency 2
10.00
01.23
Simple Positioning Stop Frequency 3
20.00
01.24
Simple Positioning Stop Frequency 4
30.00
01.25
Simple Positioning Stop Frequency 5
40.00
01.26
Simple Positioning Stop Frequency 6
50.00
01.27
Simple Positioning Stop Frequency 7
60.00
01.28
Delay Time of Simple Positioning Stop 0
0.00~600.00 sec
0.00
01.29
Delay Time of Simple Positioning Stop 1
0.00
Содержание VFD-EL series
Страница 6: ...This page intentionally left blank ...
Страница 7: ......
Страница 16: ...Revision 2016 03 6ELE V1 14 2 3 ...
Страница 25: ......
Страница 151: ......
Страница 157: ...Revision 2016 03 6ELE V1 14 B 4 Order P N BR1K0W050 Order P N BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040 ...
Страница 181: ...Appendix C How to Select the Right AC Motor Drive Revision 2016 03 6ELE V1 14 C 6 This page intentionally left blank ...