2.   CR#1, CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28 and CR#29 are reserved. 

3.   CR#2 ~ CR#5: The times to average the temperatures measured at CH1 ~ CH4. Range: K1 ~ K20. Default = 

K10. Please note that the average times set in CR#2 ~ CR#5 need to be written in only once. 

4.   CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time 

settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be the 

average of the most recent 10 temperature signals in Celsius at CH1 ~ CH4. 

5.   CR#12 ~ CR#15: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time 

settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#12 ~ CR#15 will be 

the average of the most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4. 

6.   CR #18 ~ CR #21: Displaying the present temperature in Celsius at CH1 ~ CH4 

7.   CR #24 ~ CR #27: Displaying the present temperature in Fahrenheit at CH1 ~ CH4 

8.   CR #30: Error status (see the table below): 

 

Error status 

Content 

b15 ~ b8 

b7 

b6 

b5 

b4 

b3 

b2 

b1 

b0 

Abnormal 

power 

supply K1(H’1) 

0 0 0 0 0 0 0 1 

Scale exceeds the range 
or wiring to empty external 
contact 

K2(H’2) 

0 0 0 0 0 0 1 0 

Incorrect 

mode 

setting  K4(H’4) 

0 0 0 0 0 1 0 0 

OFFSET/GAIN 

error  K8(H’8) 

0 0 0 0 1 0 0 0 

Hardware malfunction 

K16(H’10) 

0 0 0 1 0 0 0 0 

Abnormal digital range 

K32(H’20) 

0 0 1 0 0 0 0 0 

Incorrect average times 
setting 

K64(H’40) 

0 1 0 0 0 0 0 0 

Instruction error 

K128(H’80) 

reserved 

1 0 0 0 0 0 0 0 

Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the same time. 

0 = normal; 1 = error 

 

9.   CR#31: The setting of RS-485 communication address. Range: 01 ~ 255. Default = K1.   

10. CR#32: The setting of RS-485 communication speed. b0: 4,800bps; b1: 9,600bps (default); b2: 19,200bps; b3: 

38,400bps; b4: 57,600bps; b5: 115,200bps; b6 ~ b13: reserved; b14: high/low bit exchange of CRC checksum 

(only valid in RTU mode); b15: switching between ASCII mode and RTU mode. 

11. CR#33: b0 ~ b11: For returning the CR settings to default settings. 

b12 ~ b15: ERR LED definition. Default: b12 ~ b15 = 1111. 

12. CR#34: Firmware version of the model. 

13. CR#35 ~ CR#48: Parameters for system use. 

14. CR#0 ~ CR#34: The corresponding parameter address H’4064 ~ H’4086 are for users to read/write data by 

RS-485 communication. When using RS-485, the user has to separate the module with MPU first. 

a.    Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps. 

b.    Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, Even bit, 1 stop bit (7, E, 1)); RTU 

data format (8-bit, Even bit,1 stop bit (8, E, 1)). 

c.    Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data into 

register). 

d.    Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written by 

MPU through TO/DTO instruction. 

   

Temperature/Digital Curve

 

Celsius temperature measurement mode 

+6000

+3000

-2000

+600

-200 C

C

Digital output

Measured temperature input

 

 
 
 

Fahrenheit temperature measurement mode 
 
 

+11,120

+5,560

-3,280

+1,112

-328 F

F

Digital output

Measured temperature input

 

 

 

 

Trial Operation & Troubleshooting

 

™

 

LED Display

 

1.  When the module is powered for the first time, POWER LED will be on and ERROR LED will be on for 

0.5 second. After this, A/D LED will start to flash. 

2.  When the power supply is normal, POWER LED will be on and ERROR LED should be off. When the 

power supply is less than 19.5V, ERROR LED will keep being on until the power supply goes higher 

than 19.5V. 

3.  When series connected with PLC MPU, the RUN LED on the MPU will be on and A/D LED will flash. 

4.  When controlled by RS485, RS-485 LED on the module will flash after receiving the RS-485 instruction. 

5.  When the input or output value exceeds the upper bound or falls below the lower bound after conversion, 

ERROR LED will flash. 

™

 

Program Example 

M1000

FROM

K0

= H 6402 D0

'

TO

K0

FROM

K0

FROM

K0

FROM

K0

FROM

K0

END

M1002

K0

K2

K6

K12

K18

K24

D0

D10

D20

D24

D30

D34

K1

K4

K4

K4

K4

K4

 

 Read the model name from K0 and see if it is DVP04PT-H2: H’6402 

 Set the average times in CH1 ~ CH4 as D10 ~ D13. 

 If D0 = H’6402, read the average temperature (°C) measured in CH1 ~ CH4 from CR#6 ~ CR#9 and store the 4 

data in D20 ~ D23. 

 Read the average temperature (°F) measured in CH1 ~ CH4 from CR#12 ~ CR#15 and store the 4 data in D24~ 

D27. 

 Read the average temperature (°C) measured in CH1 ~ CH4 from CR#18 ~ CR#21and store the 4 data in D30~ 

D33. 

 Read the average temperature (°F) measured in CH1 ~ CH4 from CR#24 ~ CR#27 and store the 4 data in D34~ 

D37. 

   

Relevant Instructions

 

 

API 

 

 

 

78 

 

F R O M  

 

 

 

 

Read CR data in special modules 

 

 Instruction
Explanation

 

: No. of special module (m1 = 0 ~ 7)       

: CR# in special module to be read 

: Device for storing read data                   

: Number of data to be read at a time 

Program
Example

 

Read CR#24 of special module No. 0 into D0 and CR#25 into D1. Only 2 groups of data are 
read at a time (n = 2). 

 

X0

FROM

K0

K24

D0

K2

 

 
 

API 

 

 

 

79 

 

T O  

 

 

 

 

Write CR data into special module 

 

 Instruction
Explanation

 

: No. of special module (m1 = 0 ~ 7)     

: CR# in special module to be written 

: Data to be written into CR                     

: Number of data to be written at a time 

Program
Example

 

Use 32-bit instruction DTO to write the content in D11 and D10 into CR#7 and CR#6 of special 
module No. 0. Only 1 group of data is written in at a time (n = 1). 

X0

DTO

K0

K6

D10

K1

 

Remarks

 

 Operand rules 

1. 

: The No. of special modules connected to PLC MPU. No. 0 is the module closest to te 

MPU. Maximum 8 modules are allowed to connected to a PLC MPU and they will not occupy 

any I/O points. 

2. 

: CR#. CR (control register) is the 49 16-bit memories built in the special module, 

numbered in decimal as #0 ~ #48. All operation status and settings of the special module are 

contained in the CR. 

3.  FROM/TO instruction is for reading/writing 1 CR at a time. DFROM/DTO instruction is for 

reading/writing 2 CRs at a time. 

CR #10

CR #9

L ower  1 6- bi t

Desig nated CR number

Hi gher 16 -b it

 

4.  Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit 

instructions mean the same. 

 

D0
D1
D2
D3
D4
D5

CR #5
CR #6
CR #7
CR #8
CR #9
CR #10

D0
D1
D2
D3
D4
D5

CR #5
CR #6
CR #7
CR #8
CR #9
CR #10

Designated device

Designated CR

Designated device Designated CR

16-bit instruction  when n=6

32-bit instruction when n=3

 

 M1083 for switching instruction modes in EH2 series models 

1.  When M1083 = Off, during the execution of FROM/TO instruction, all external or internal 

interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO 

instruction finishes its execution. FROM/TO instruction can also be used in an interruption 

subroutine. 

2.  When M1083 = On and an interruption signal occurs during the execution of FROM/TO 

instruction, the interruption will be processed first (with a 100us delay) and the execution of 

FROM/TO will be stopped. After the interruption subroutine finishes its execution, the 

program will jump to the next instructio of FROM/TO. FROM/TO cannot be used in an 

interruption subroutine. 

 

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 