Chapter 2 Installation
AFE2000 Series
2-9
NOT E
※
The mounting clearances shown in the left figure are
NOT
for installing the
drive in a confined space (such as cabinet or electric box). When installing
in a confined space, besides the same minimum mounting clearances, it
needs to have the ventilation equipment or air conditioner to keep the
surrounding temperature lower than the operation temperature.
※
The following table shows heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number the drives.
※
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
※
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Air flow rate for cooling
Power Dissipation
Flow Rate (cfm)
Flow Rate (m
3
/hr)
Power Dissipation
Model No.
External Internal
Total
External Internal
Total
Loss External
(Heat sink)
Internal
Total
AFE075A23A
66
14
80
112
24
136
249
86
335
AFE150A23A
166
12
178
282
20
302
455
161
616
AFE220A23A
146
12
158
248
20
268
649
216
865
AFE370A23A
179
30
209
304
51
355
1091
220
1311
AFE075A43A
40 14 54 68 24 92
216
76 292
AFE150A43A
58 14 73 99 24 124 396 122
518
AFE220A43A 99 21 120 168 36 204
476
158 635
AFE370A43A
179 30 209 304 51 355
809
184 993
AFE450A43A
179 30 209 304 51 355
929
218
1147
AFE750A43A
186 30 216 316 51 367 1408 334
1742
※
The required airflow shown in chart is for installing single drive in a
confined space.
※
When installing the multiple drives, the required air volume should
be the required air volume for single drive X the number of the
drives.
※
The heat dissipation shown
in the chart is for installing
single drive in a confined
space.
※
When installing the multiple
drives, volume of heat
dissipation should be the
heat dissipated for single
drive X the number of the
drives.
※
Heat dissipation for each
model is calculated by rated
voltage, current and default
carrier.
Содержание AFE075A23A
Страница 1: ...5012604300 AFE0 2011 02 15 ...
Страница 8: ...Chapter 1 Introduction AFE2000 Series 1 6 Digital Keypad KPC CE01 ...
Страница 12: ...Chapter 2 Installation AFE2000 Series 2 10 This page is intentionally left blank ...
Страница 22: ...Chapter 5 Control Terminals AFE2000 Series 5 20 This page is intentionally left blank ...
Страница 31: ...Chapter 6 Optional Accessories AFE2000 Series 6 29 ...
Страница 42: ...Chapter 6 Optional Accessories AFE2000 Series 6 40 This page is intentionally left blank ...
Страница 60: ...8 58 This page is intentionally left blank ...
Страница 64: ...Chapter 9 Digital Keypad AFE2000 Series 9 62 This page is intentionally left blank ...
Страница 74: ...Chapter 10 Summary of Parameter Settings AFE2000 Series 10 72 This page is intentionally left blank ...
Страница 110: ...Chapter 13 Fault Codes and Descriptions AFE2000 Series 13 108 This page is intentionally left blank ...