Chapter 13 Fault Codes and Descriptions
AFE2000 Series
13-104
Fault Name
Fault Descriptions
Corrective Actions
LvS
Lv at stop
Fault
DC BUS voltage is less than
Pr.03-00 at stop
1.
Check if the input voltage is normal
2.
Check for possible sudden load
oH1
IGBT over heat
Fault
IGBT overheating
IGBT temperature exceeds
protection level
1~50HP: 105
; 60~100HP:
℃
110
℃
1. Ensure that the ambient temperature
falls within the specified temperature
range.
2.
Make sure that the ventilation holes are
not obstructed.
3. Remove any foreign objects from the
heatsinks and check for possible dirty
heat sink fins.
4.
Check the fan and clean it.
5. Provide enough spacing for adequate
ventilation.
oH2
Heat Sink oH
Fault
Heatsink overheating
Capacitance temperature exceeds
protection level.
1~50HP: 80
; 60~100HP: 65
℃
℃
1. Ensure that the ambient temperature
falls within the specified temperature
range.
2. Make sure heat sink is not obstructed.
Check if the fan is operating
3. Check if there is enough ventilation
clearance for AC motor drive.
tH1o
Thermo 1 open
Fault
IGBT Hardware Error
Return to the factory
tH2o
Thermo 2 open
Fault
Capacitor Hardware Error
Return to the factory
oL
Over load
Fault
Overload
The AC motor drive detects
excessive drive output current.
1. Increase AFE2000 output capacity.
Replace with the next higher power
AFE2000 unit.
cF1
EEPROM write err
Fault
Internal EEPROM can
not be programmed or
Internal EEPROM can
not be read.
1. Press “RESET” key to the factory setting
2. Return to the factory.
cF2
EEPROM read err
Fault
Internal EEPROM can not be
read.
1. Press “RESET” key to the factory setting
2. Return to the factory.
Содержание AFE075A23A
Страница 1: ...5012604300 AFE0 2011 02 15 ...
Страница 8: ...Chapter 1 Introduction AFE2000 Series 1 6 Digital Keypad KPC CE01 ...
Страница 12: ...Chapter 2 Installation AFE2000 Series 2 10 This page is intentionally left blank ...
Страница 22: ...Chapter 5 Control Terminals AFE2000 Series 5 20 This page is intentionally left blank ...
Страница 31: ...Chapter 6 Optional Accessories AFE2000 Series 6 29 ...
Страница 42: ...Chapter 6 Optional Accessories AFE2000 Series 6 40 This page is intentionally left blank ...
Страница 60: ...8 58 This page is intentionally left blank ...
Страница 64: ...Chapter 9 Digital Keypad AFE2000 Series 9 62 This page is intentionally left blank ...
Страница 74: ...Chapter 10 Summary of Parameter Settings AFE2000 Series 10 72 This page is intentionally left blank ...
Страница 110: ...Chapter 13 Fault Codes and Descriptions AFE2000 Series 13 108 This page is intentionally left blank ...