Setup & Configuration
Network Communications
On an MS/TP network, BACstats communicate at a default speed of 76,800 bps. Refer to the DNT-
T221BX-FCU Release 4 Application Guide for network installation details.
Flash Programming
BACstat III offers flash loadable firmware across a network connection. It is supported by Flashloader
V3.33+, and operates the same way as other Delta controllers. Ensure that all databases have been
backed up prior to upgrading the flash firmware. Refer to the Flashloader User Guide
for further details on
using the Flashloader to upgrade the firmware on the BACstat III product.
Device Configuration (Keypad)
To configure BACstats with ORCAview OWS, refer to
OWS Functions
on page 25.
Configuration Menu User Access
Access to the Configuration Menu is protected by an access code or PIN. You must enter the valid PIN
before access is granted:
•
First press and hold
the Up Arrow (▲), and then the Down Arrow (▼). Hold them both down for at
least 5 seconds.
•
When
is displayed, enter a valid PIN or access code, a pre-configured 4-digit code, to gain
access to the Configuration Menu. The buttons on the left side of the BACstat have a value of 0,
while the buttons on the right side have a value of 1. Press the proper button sequence to match
the password.
•
The default PIN is
1011
. The PIN access code, contained in AV31, can be changed through the
OWS, when the BACstat is connected to an MS/TP network.
•
is displayed to indicate successful access to Configuration mode. If you fail to enter a valid
code (or if you do not press a button within about 10 seconds), the process is aborted and the
device returns to normal display mode.
•
The BACstat exits the Configuration Menu, and returns to normal display mode if a button is not
pressed for 2 minutes.