Installation and Setup
Installing a PS6500 Array
2–15
Environmental Requirements
You must meet these environmental requirements for a PS6500 array:
•
Only operate an enclosure from a power source with a voltage range of 100 to
240 VAC.
•
Make sure your power source has sufficient electrical overload protection.
•
In North America, connect the enclosure to a source of power with over-
current protection provided by a double pole 20A or less (LISTED circuit
breaker to UL489). In Europe, the over-current protection must be provided
by 20A or less (IEC circuit breakers).
•
Make sure there is sufficient space for air flow in front of and behind the array
and make sure that the location is properly vented.
•
Review the technical specifications inTable 2-6 to make sure your
environment supports its requirements.
Table 2-6: PS6500 Technical Specifications
Component
Requirement
Weight without disk drives
77 pounds (35kg)
Weight with disk drives
177 pounds (80kg)
Operating temperature
41 to 95 degrees F / 5 to 35 degrees C
Storage temperature
34 to 140 degrees F / 1 to 60 degrees C
Operating altitude
0 to 10,000 feet (0 to 3048 meters)
Operational relative humidity
20 percent to 80 percent non-condensing
Storage relative humidity
5 percent to 80 percent non-condensing
Thermal output (fully-loaded array) 3400 BTU/hour
Operational shock
5G peak 1/2 sin, for 10ms
Operational vibration
Random 0.21grms 5 - 500 Hz
Input voltage
100 to 240 VAC (auto-sensing)
Input frequency
50 - 60Hz
System input power
1400 VA (maximum)
Each power supply
440 watts DC output
Maximum input power: 0.7 KVA
Input current: 7 – 3.5A