Third-party rack requirements
Customers who want to assemble an ECS Appliance using their own racks must
ensure that the racks meet the following requirements listed in
on page 68.
RPQ is required for the following additional scenarios related to customer-provided
rack:
l
Single model that is installed in multi-racks.
l
The U-Series DAE Cable Management Arms (CMA) cannot be installed due to
third-party rack limitations.
l
Transfers from Dell EMC to customer rack.
Option: Customer rack enables the adjustment of rear rails to 24 inches so that
Dell EMC fixed rails can be used. RPQ is not required if all third-party rack
requirements in
Table 41 Third-party rack requirements
Requirement Category
Description
Cabinet
44 inches minimum rack depth.
Recommended 24 inches wide cabinet to provide room for cable routing on the sides of
the cabinet.
Sufficient contiguous space anywhere in the rack to install the components in the
required relative order.
If a front door is used, it must maintain a minimum of 1.2 inches of clearance to the
bezels. It must be perforated with 50% or more evenly distributed air opening. It should
enable easy access for service personnel and allow the LEDs to be visible through it.
If a rear door is used, it must be perforated with 50% or more evenly distributed air
opening.
Blanking panels should be used as required to prevent air recirculation inside the cabinet.
There is a recommended minimum of 42 inches of clearance in the front and 36 inches of
clearance in the rear of the cabinet to allow for service area and proper airflow.
NEMA rails
19 inches wide rail with 1U increments.
Between 24 inches and 34 inches deep.
NEMA round and square hole rails are supported.
NEMA treaded hole rails are NOT supported.
NEMA round holes must accept M5 size screws.
Special screws (036-709-013 or 113) are provided for use with square holes rails.
Square hole rails require M5 nut clips that are provided by the customer for third-party
rack provided.
Power
The AC power requirements are 200–240 VAC +/- 10% 50–60 Hz.
Vertical PDUs and AC plugs must not interfere with the DAE and Cable Management
arms requiring a depth of 42.5 inches.
Third Party Rack Requirements
68
D- and U-Series
Hardware Guide
Содержание ECS D Series
Страница 1: ...Dell EMC Elastic Cloud Storage ECS D and U Series Hardware Guide 302 003 477 09 ...
Страница 8: ...TABLES 8 D and U Series Hardware Guide ...
Страница 25: ...CHAPTER 2 Servers l ECS Appliance servers 26 l Rack and node host names 30 Servers 25 ...
Страница 32: ...Servers 32 D and U Series Hardware Guide ...
Страница 33: ...CHAPTER 3 Switches l ECS Appliance switches 34 Switches 33 ...
Страница 44: ...Switches 44 D and U Series Hardware Guide ...
Страница 59: ...Figure 31 U Series disk layout for 30 disk configurations Gen1 Gen2 Disk Drives Voyager DAE 59 ...
Страница 67: ...CHAPTER 5 Third Party Rack Requirements l Third party rack requirements 68 Third Party Rack Requirements 67 ...
Страница 70: ...Third Party Rack Requirements 70 D and U Series Hardware Guide ...
Страница 88: ...Power Cabling 88 D and U Series Hardware Guide ...
Страница 89: ...CHAPTER 7 SAS Cabling l U Series SAS cabling 90 l D Series SAS cabling 93 SAS Cabling 89 ...
Страница 91: ...Figure 52 U Series Gen2 SAS cabling for eight node configurations SAS Cabling U Series SAS cabling 91 ...
Страница 94: ...Figure 55 D Series SAS cabling for eight node configurations SAS Cabling 94 D and U Series Hardware Guide ...
Страница 98: ...Figure 60 Public switch cabling for U and D Series Network Cabling 98 D and U Series Hardware Guide ...
Страница 99: ...Figure 61 U Series and D Series network cabling Network Cabling Network cabling 99 ...
Страница 107: ...Figure 65 C Series public switch cabling for the upper segment from the rear Network Cabling Network cabling 107 ...
Страница 109: ...Figure 66 C Series private switch cabling for the lower segment from the rear Network Cabling Network cabling 109 ...