40
iTR326H operation
default interface
Display the default interface when the ETU is powered on
press the button
or the corresponding topic key under each topic menu to
return to the default interface
If there is no key operation within 5 minutes, the box cursor will automatically
indicate the current maximum phase
under the non fault pop-up interface, if there is no key operation within 20 minutes, it
will automatically return to the default interface
measurement menu
Press
to enter the measurement main menu
Press
or
to return to the default interface
In other non fault and non edit interfaces, press
to jump to the "measurement" menu
system parameter setting menu
Press
to enter the system parameter setting menu
Press
to return to the default interface
In other non fault and non edit interfaces, press
to jump to "system parameter
setting" menu and "history and maintenance" menu