36
Short circuit instantaneous protection characteristics
Action threshold of short circuit instantaneous protection
<0.85Ii:No action
>1.15Ii:action
I
R
Current setting range:2In,3In,4In,6In,8In,10In,12In,15In+OFF,
Note:
Allowable error of action time≤50ms
Earth fault protection characteristics
Action threshold of earth fault protection
<0.9Ig:No action
>1.1Ig:action
≥1.1Ig:Delay action
Current
setting
A
B
C
D
E
F
G
H
OFF
In<1250
0.2In
0.3In
0.4In
0.5In
0.6In
0.8In
0.9In
In
In≥1250
500A
600A
700A
800A
900A
1000A 1100A 1200A
current
Action time
tg(s)
Inverse time
limit
Action
characteristics
t=
( )
╳
𝑡𝑔
Setting time s
0.1
0.2
0.3
0.4
Timing limit,
minimum time
is return time
Setting time s
0.1
0.2
0.3
0.4
Minimum s
0.08
0.14
0.23
0.35
Maximum s
0.14
0.2
0.32
0.5
Note:
I
J
:
Setting value of grounding protection,When In≥1250A,I
J
=1200A; When
In<1250A,I
J
=In;When I≥I
J
,fixed time limit;When Ig<I<I
J
,inverse time
limit.
I:
Fault current value
t:
Fault action delay time
tg:
Setting value of inverse time limit of grounding
Allowable error of inverse time limit action time±20%
(off of time period means I
2
t off, i.e. inverse time limit is closed, which is fixed time limit;
use off of current gear to close short time delay protection function)
Factory setting value of intelligent controller
Trip
curve I
2
t
Long time delay
Short time delay
instanta
neous
Earth fault
Thermal
memor
y
I
R
t
R
Isd
ts
Ii
Ig
tg
1In
30s
6In
0.2s
10In
Gear G
(4P, 3P +
n)
Off (3P)
0.4s
20min
Note: the grounding fault protection of 3p product is in off state (off gear) from the factory, which
can be adjusted by the user according to the actual situation.
Note: refer to the website for instructions of iTR326 series Electronic trip unit( www.delixi-
electric.com )
Product center > power distribution > ACB > CDW3