Nordic Zone Salad Bar Service and Installation Manual

For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com

2

Nordic Zone Salad Bar Service and Installation Manual

3

For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com

In most instances, the salad bar units will arrive at the job site 

uncrated, and caution must be taken not to damage any exterior 

surfaces when moving into position.  All internal components 

including glass and mirrors will be shipped intact within the unit.

The area where the salad bar is to be located must be clean and the 

floor level to assure a satisfactory installation.

In the appropriate location, units must be leveled with the finished 

work height top of Corian

®

 to be approximately 34” above finished 

floor.  Make sure units are level left to right as well as front to back.  

The units are mounted on 6” high legs which can be adjusted up to 1”.

Corian

®

 adhesive (supplied) is to be applied between Corian

®

  

surfaces where they adjoin at center for proper moisture sealing.

Once the Corian

®

 adhesive has been applied the units are ready to 

be connected together where noted “spline here.”  The locations are 

directly behind the front nosing, below the upper front air diffuser, 

and at the rear of the unit.  Fasteners will be pre-installed within the 

spline locations.  Clean the units.  Remove any excess silicone or 

adhesive that may have squeezed out after splining units together.  

With sufficient help (4-5) individuals, slowly push the connected units 

“evenly” back to the wall at the rear.  Make sure that all stubbed out 

electrical, refrigeration lines, and plumbing lines clear the cabinet 

structure.  If not, make any necessary adjustments to clear these 

components.  Once the units are secure against the wall at the rear, 

double check for level.

Locate and install Corian

®

 rear and side splashes using adhesive 

supplied.  It may be necessary to trim pieces slightly to fit.

REFRIGERATION INSTALLATION

If the condensing units are to be set on the roof of the building, it 

must be mounted on beams supplied by the roofing contractor or the 

refrigeration contractor.

The condensing units must be a minimum of three feet apart to assure 

proper air flow.  Before the salad bar units arrive the refrigeration lines 

must be installed from the condensing units down through the ceiling 

and the rear wall and stubbed out per the drawing supplied to the 

installer.  The suction line should be 5/8 inch and the liquid line should 

be 3/8 inch for most installations.  The pipe insulation should be 1/2 

inch wall thickness.  A “p” trap must be installed at the lowest point 

of the refrigeration lines.  The electrical power supply must also be 

stubbed through the rear wall.

The liquid line should be insulated if exposed to sunlight on roof 

installations.  All refrigeration lines must be secured to prevent 

excessive vibrating or kinking of the copper tubing.  Drain lines must 

be installed to the drain stub on the bottom of the evaporator housing.  

The drain must have proper slope to insure good drainage from the 

evaporator pan.  A minimum vacuum of 200 microns must be reached 

before charging the units with R-404A refrigerant.  The system must 

be charged under a heat load with R-404A until the sight glass is clear.  

Normal installations will require approximately 9lbs. of refrigerant for 

each system.

All panels and covers must be installed in the proper locations and 

the defrost timer must be set for the proper time.  Defrost time for 

normal installations should be 15 minutes every three hours and the 

thermostat setting should be for 37º degrees box temperature.

NOTE: do not change setting of defrost timer or 

thermostat.  See page #4 for complete operation 

instructions.

INSTALLATION

On/Off Switch located 

behind the center 

panel.

Thermostat located 

behind the On/Off 

switch panel.

Содержание Nordic Zone Cold Food Bars

Страница 1: ...Manual Please read this manual completely before attempting to install or operate this equipment Notify carrier of damage Inspect all components immediately See page 2 August 2003 IMPORTANT INFORMATIO...

Страница 2: ...re should be taken during unloading so the equipment is not damaged while being moved into the building 1 Visually inspect the unit Any damage should be noted and reported to the delivering carrier im...

Страница 3: ...ied It may be necessary to trim pieces slightly to fit REFRIGERATION INSTALLATION If the condensing units are to be set on the roof of the building it must be mounted on beams supplied by the roofing...

Страница 4: ...ning product available to clean glass mirrors on the salad bar Typically soap and water or ammonia will clean the glass sufficiently If stronger solutions are required be sure to use products designed...

Страница 5: ...change the setting of the defrost timer or thermostat Adjustments are to be made by qualified service technicians only Defrost cycles are factory preset and should not require field adjustments In th...

Страница 6: ...USE IKTK R 5 BLACK BLACK BLUE BLACK BLUE 120v TO 24v TRANSFORMER HEATING ELEMENTS GREEN END LAMP WHITE BLACK LAMP 1 LAMP 2 Y Y R R B B R B B Y Y R BALLAST 120v INPUT 227v OUTPUT GREEN WHITE BLACK RAIL...

Страница 7: ...URE LIGHT ON OFF SWITCH NEUTRAL L1 GND WHITE RED BLUE XF FUSE OFNM 15 X1 X2 RED WHITE BLACK HF FUSE IKTK R 5 H4 H2 H3 H1 H1 FUSE IKTK R 5 BLACK BLACK BLUE BLACK BLUE 120v TO 24v TRANSFORMER HEATING EL...

Страница 8: ...e 3516173 Fan guard 2162691 Fan motor ONE SIDE OF THE 123 Remote PART NUMBER DESCRIPTION 323457 Control knob ring guard 2194620 Fan safety switch RTP00013 34 Fluorescent bulb RTP00034 UCM 8 Fluorescen...

Страница 9: ...Nordic Zone Salad Bar Service and Installation Manual 9 For customer service call 800 733 8829 800 773 8821 Fax 989 773 3210 www delfield com FULL VIEW 207 Switch and defrost locations...

Страница 10: ...rdic Zone Salad Bar Service and Installation Manual For customer service call 800 733 8829 800 773 8821 Fax 989 773 3210 www delfield com 10 FULL VIEW 123 10 35 10 35 135 32 3 22 20 20 123 5 83 5 102...

Страница 11: ...AMINATE FRONT CLEAR TEMPERED GLASS SNEEZE GUARD LAMINATE TOP 1 CHROME HINGE 1 2 GLASS STOP POWDER COATED ARM LAMINATE END REAR SPLINE DETAIL 18 SPLINE TOP LAMINATE FRONT 1 S S SEAMS REAR OF UPPER STRU...

Страница 12: ...Nordic Zone Salad Bar Service and Installation Manual For customer service call 800 733 8829 800 773 8821 Fax 989 773 3210 www delfield com 12 NSF Official Listing For Lighting System...

Страница 13: ...REPLACE Thermostat Contactor Relay Infinite Switch Transformer Door Jamb Switch Evaporator Condenser Fan Motor and Blade Solenoid Coil Circulating Fan Motor and Blade Hi limit Thermal Protector Switch...

Страница 14: ...PLICABLE TIME AND MATERIALS RATES CONSIDER CUSTOMER MAY INITIATE A SERVICE AGREEMENT WITHOUT PARTS COVERAGE If shipment of a replacement part is requested prior to the arrival in the Delfield factory...

Страница 15: ...altered defaced or removed This Warranty does not apply to a Motor Compressor in any Unit that has been moved from the location where it was originally installed The addition of methyl chloride to th...

Страница 16: ...Nordic Zone Salad Bar Service and Installation Manual For customer service call 800 733 8829 800 773 8821 Fax 989 773 3210 www delfield com 16 NOTES...

Страница 17: ...272 7358 fax serves AR LA NM OK TX 7 Stove Parts Supply GCS Service 9923 S W 178th St Vashon WA 98070 888 872 2465 206 463 1772 206 463 4431 FAX serves AK HI ID MT OR WA 12 Performance Refrigeration...

Отзывы: