Operation
Section 3
EVAPORATOR FAN OPERATION
During normal operation the evaporator fan may cycle
and/or pulse independently of the compressor. Consult
Technical Support at 1-844-724-CARE if you are unsure of
the proper function.
Cooling Cycle
Defrost Cycle
Compressor On
Compressor Off
Compressor Off
Evap Fan On
Evap Fan Cycles On
2-Min, Off 2-Min
Evap Fan On
115Volt F15 Pressure Control
F15 display cases have a high pressure limiting device.
Under severe overloading conditions, or in the event of a
condenser fan failure or a plugged or blocked condenser,
this device may shut down the refrigeration system. This
device will automatically reset, but determining the cause
of the high pressure condition should be investigated by a
qualified refrigeration technician.
,
Caution
In attempting to adjust the pressure control, you can
do damage to your unit. Please contact Kitch1
(844) 724-2273 or your local service agent. Delfield is
not responsible for charges incurred while having the
pressure control adjusted.
Factory Recommended Settings
Cut-in
20#
Cut-out
5#
Differential
15#
F15 Base Pressure Control