background image

1

SYSTEM DESIGN

Systems Design is the process of defining the architecture,
components, modules, interfaces, and load data for a system
to satisfy specified requirements. For a solar system these
components are the PV modules, inverter/charge controller
& batteries, as well as the different interfaces of those 
components.
To properly size a battery/battery bank for a renewable energy
system the following parameters are required:

 Load

– Amount of DC current (Amps, Ah) or power  (Watts,

Wh) a battery is required to supply to a DC load or AC loads
through an inverter.

 Time

– expressed in hours the battery will be required to 

provide the load.

 System Voltage

– DC system operating voltage

 Ambient Temperature

– Average temperature of battery

room or enclosure. 

 Depth of Discharge (DoD)

– The proportion of energy that

has been removed from a battery; typically in a 24hr period 

 

Example:

100% DoD is removing all 
of the energy from a battery.

 Autonomy

– Length of time PV system can provide energy to

load without energy from PV array

 

Design Margin

- Factor (typically expressed as a percentage)

to allow for future load additions.

A Renewable Energy Worksheet is provided in 

Appendix A

listing the above requirements along with additional information
requirements

BATTERY OPERATION

There are several factors that affect the operation of the battery
concerning its ability to deliver capacity and life expectancy.

Temperature

Many chemical reactions are effected by temperature, and
this is true of the reaction that occurs in a storage battery.
The chemical reaction of a lead-acid battery is slowed down
by a lowering of the electrolyte temperature that results in
less capacity. A battery that will deliver 100% of rated 
capacity at 77° F will only deliver approximately 65% of 
rated capacity at 32°F. 
At temperatures below 32°F (0°C) a battery can freeze
dependent on the DoD (Depth of Discharge). The higher the
DoD, the closer to 32°F (0°C) before the battery will freeze.
The graph in Appendix C should be consulted to verify the
DoD of the battery / battery bank at the end of the discharge

will not be susceptible to freezing in a particular application.
If the electrolyte would freeze, the internal damage would be
irreversible requiring the battery to be replaced.
Excessive heat will increase the natural corrosion factors of a
lead-acid battery. This increase corrosion of the positive plates
contributes greatly to reducing the overall life of the battery.

Depth of Discharge (DoD)

Depth of discharge is a function of design. The deeper the
discharge per cycle, the shorter the life of the battery. A
cycle is a discharge and its subsequent recharge regardless
of depth of discharge.
Systems should be designed for shallow discharges. The
result of shallower discharges is typically a larger capacity
battery at prolonged battery life.
A Cycle vs. DoD chart should be consulted to determine the
number of cycles at a specific DoD and the projected life in
years the battery / battery system will provide prior to need-
ing replacement.

Charging

Majority of battery capacity/life issues can be traced to
improper charging. Improper charging settings may lead to
an overcharging or undercharging condition.
Typical Inverters/Charge Controllers charging lead-acid 
batteries use 3 stage charging: Bulk, Absorption and Float
with an optional equalize stage. 

See Appendix B for an

example of a typical 3-stage charging curve.

Inverter/Charge Controller Settings 

Proper Inverter/Charge Controller settings are necessary 
to ensure peak battery performance and life. All bulk,
absorption, float and equalize settings should be verified they
are within the battery manufacturers settings. These settings 
are included but not limited to; voltage, current and time.
Consult individual battery Installation & Operating manuals
for inverter/charge controller setting recommendations.

Default settings should not be presumed to be correct. 
For battery systems located in an uncontrolled temperature
environment, temperature compensation must be used.

Bulk

Current is applied to the batteries at the maximum safe rate
they will accept until voltage rises to near (80-85%) full charge
level. The battery voltage rises because the charging current
that is provided by the battery charger is replenishing its 
internal charge capacity. The charger current is flat (constant)
and the battery voltage is rising.  
Maximum allowable charge voltage & current allowed by 
the battery manufacturer should be used to ensure the most
energy is returned within the bulk stage.

Renewable Energy applications that depend on battery power as part of the system operation must be at

maximum performance at all times. To ensure this high rate of performance is achieved, the battery charging

system must be set properly. A battery/battery bank that is undercharged or overcharged will affect the 

battery system performance & life, as well as the performance of the entire system.

Key factors that affect a batteries ability to provide the capacity and long life that is expected are: System

Design, Storage, Temperature, Depth of Discharge (DoD), Charging and Maintenance.

Содержание SOLAR Monoblock VRLA System

Страница 1: ...Monoblock VRLA System Installation Operating Manual ...

Страница 2: ...n X Unpacking X Storage X Installation General X Grounding X System Operation Charging X Charging Parameters X Charge Current X State of Charge X Record Keeping Maintenance Annual Inspection X Rectifier Ripple X Capacity Testing X Glossary Appendix A Renewable Energy Worksheet X Appendix B Example of Typical 3 Stage Charger X Appendix C Depth of Discharge vs Freezing PointX Appendix D Capacity vs ...

Страница 3: ...of Discharge DoD Depth of discharge is a function of design The deeper the discharge per cycle the shorter the life of the battery A cycle is a discharge and its subsequent recharge regardless of depth of discharge Systems should be designed for shallow discharges The result of shallower discharges is typically a larger capacity battery at prolonged battery life A Cycle vs DoD chart should be cons...

Страница 4: ...ing the necessary maximum charge current for the system If the calculation shows the absorption time is greater than the minimum average peak sun hours for the installation location the amount of available current to the batteries should be increased which could be accomplished by a larger array or a secondary power source such as a generator Charge Current Verification FLOODED C20 x 0 44 charge c...

Страница 5: ...equate space and accessibility for taking individual battery or cell voltage hydrometer readings and adding water should be considered If installed in an earthquake seismic zone battery racking system must be of sufficient strength and adequately anchored to the floor Battery rack design and anchoring should be reviewed by a structural engineer Ventilation It is the responsibility of the installer...

Страница 6: ...ing no back up energy source Wiring connection assessment difficult to follow with multiple wirings connected to same battery terminal increasing chance of re connection wiring errors Common Bus Wiring a wiring scheme in which same polarity terminals are connected to a single termination point All inter connecting wiring should be of same length to minimize volt age drop Advantages Cables can be o...

Страница 7: ...ring dry and clear of tools and other for eign objects 4 Provide adequate ventilation per IEEE standard 1187 and or local codes and follow recommended charging voltages 5 Never remove or tamper with the pressure relief valves except for cell replacement Warranty void if vent valve is removed 6 Inspect flooring and lifting equipment for functional adequacy 7 Adequately secure cell modules racks or ...

Страница 8: ...g gently with a non metallic brush or pad before installing connectors No Ox ID grease can be used but is not required 3 Install all electrical connectors cables and bolting hard ware loosely to allow for final alignment of batteries Torque to manufacturer recommendations 4 After torquing read the voltage of the battery string to ensure the individual batteries are connected correctly The total vo...

Страница 9: ...tage readings are affected by dis charge and recharges for cyclic applica tions the battery ies must be in a fully charged condition prior to taking readings Batteries should be within 0 30 volts 0 15 volts for 6V of the average battery float voltage 3 Record charger voltage 4 Record the ambient temperature 5 Record individual battery ohmic readings 6 Record all interunit and terminal connection r...

Страница 10: ...nd temperature The capacity of a battery is not a constant value and is seen to decrease with increasing discharge rate C20 Battery capacity measured in Ah amp hour at the 20hr rate End Voltage The minimum voltage at which a DC system will operate Flooded A battery in which the products of electrolysis and evaporation are allowed to escape to the atmosphere as they are generated Electrolyte is fre...

Страница 11: ...9 APPENDIX A Completing all parameters ensures accurate battery sizing Worksheet to be submitted to sales representative for battery recommendation ...

Страница 12: ...10 APPENDIX B Example of typical 3 stage charger ...

Страница 13: ...11 APPENDIX C Depth of Discharge vs Freezing Point ...

Страница 14: ...12 APPENDIX D Capacity vs Operating Temperature ...

Страница 15: ...13 APPENDIX E Voltage Compensation Chart 0 1 2 3 4235 4 65 Note 1 Above values based on 12 volt battery 2 Divide above values in half for 6 volt battery ...

Страница 16: ...14 APPENDIX F Charging Current vs Charging Time chart Discharge Voltage Curve ...

Страница 17: ...APPENDIX G ...

Страница 18: ...ufacturing Co Subsidiary 1 800 372 9253 www mkbattery com e mail sales mkbattery com www dekabatteries com All data subject to change without notice No part of this document may be copied or reproduced electronically or mechanically without written permission from the company ...

Отзывы: