background image

®

APPENDIX B

VOLTAGE COMPENSATION CHART

°C

Float

Equalize

°F

>35

13.38

14.28

>95

34

13.39

14.29

93.2

33

13.40

14.30

91.4

32

13.42

14.32

89.6

31

13.43

14.33

87.8

30

13.44

14.34

86.0

29

13.45

14.35

84.2

28

13.46

14.36

82.4

27

13.48

14.38

80.6

26

13.49

14.39

78.8

25

13.50

14.40

77.0

24

13.51

14.41

75.2

23

13.52

14.42

73.4

22

13.54

14.44

71.6

21

13.55

14.45

69.8

20

13.56

14.46

68.0

19

13.57

14.47

66.2

18

13.58

14.48

64.4

17

13.60

14.50

62.6

16

13.61

14.51

60.8

15

13.62

14.52

59.0

14

13.63

14.53

57.2

13

13.64

14.54

55.4

12

13.66

14.56

53.6

11

13.67

14.57

51.8

<10

13.68

14.58

<50

12mV per ˚C

Содержание fahrenheit

Страница 1: ...tring is defined as a series connected electrical system comprised of batteries individual 12 volt units Protective Equipment Although VRLA batteries can vent or leak small amounts of electrolyte electrical safety is the principle but not the only concern for safe handling Per IEEE 1188 recommendations the following minimum set of equipment for safe handling of the battery and protection of person...

Страница 2: ...t the time of actual unloading each package should be visually inspected for any possible damage or electrolyte leakage If either the entire shipment should be conducted and noted on the bill of lading Record receipt date inspection date and notify carrier of any damage Unpacking 1 Always wear eye protection 2 Check all batteries for visible defects such as cracked containers loose terminal posts ...

Страница 3: ...completed for each refresh charge 8 Batteries shall not be stored beyond 12 months Storing beyond 12 months will affect warranty 9 If the storage refresh requirements cannot be met contact East Penn Reserve Power s Product Support group for alternate instructions INSTALLATION General Caution should be taken when installing batteries to insure no damage occurs The battery string cabinet tray rack e...

Страница 4: ...Mfg Safe installation of any venting equipment is the responsibility of the installer BATTERY ASSEMBLY ALWAYS WEAR EYE PROTECTION 1 Set up the battery string so that the positive post of one battery is connected to the negative post of the next battery for all series connections The inter battery connector contact surfaces shall be cleaned by rubbing gently with a non metallic brush or pad before ...

Страница 5: ...ections properly to 100 in lb 5 Micro ohm readings should be taken across every connection Refer to meter manufacturer s instructions for proper placement of probes If any reading differs by more than 20 from its initial installation value re torque the connection to 100 in lb 5 If reading remains high clean contact surfaces according to Step 1 under Battery Assembly Failure to maintain proper rec...

Страница 6: ... 20 from initial readings taken retorque the connection Retourque value is equal to initial torque value as indicated in BATTERY ASSEMBLY section Recheck the micro ohm reading If the reading remains high clean the contact surface according to installation portion of this manual 1 Other Maintenance Inspection intervals follow IEEE 1188 Battery Cleaning Do not use any chemical compounds to clean bat...

Страница 7: ...y 6 Battery 7 Battery 8 Battery 9 Battery 10 Battery 11 Battery 12 Battery 13 Battery 14 Battery 15 Battery 16 Battery 17 Battery 18 Battery 19 Battery 20 Battery 21 Battery 22 Battery 23 Battery 24 ALL FIELDS TO THE RIGHT OF THE CELL NUMBER ABOVE MUST BE COMPLETED EPM ORDER NUMBER WILL APPEAR ON THE SHIPPING LABEL ON THE CARTON COVERING EACH PALLET OF CELLS TO ENSURE CONTINUATION OF WARRANTY SUBM...

Страница 8: ...84 2 28 13 46 14 36 82 4 27 13 48 14 38 80 6 26 13 49 14 39 78 8 25 13 50 14 40 77 0 24 13 51 14 41 75 2 23 13 52 14 42 73 4 22 13 54 14 44 71 6 21 13 55 14 45 69 8 20 13 56 14 46 68 0 19 13 57 14 47 66 2 18 13 58 14 48 64 4 17 13 60 14 50 62 6 16 13 61 14 51 60 8 15 13 62 14 52 59 0 14 13 63 14 53 57 2 13 13 64 14 54 55 4 12 13 66 14 56 53 6 11 13 67 14 57 51 8 10 13 68 14 58 50 12mV per C ...

Страница 9: ...MITS HT30 5 5 1 6 HT80ET 13 1 3 9 HT145ET 26 0 7 8 HT170ET 30 4 9 1 HT200ET 36 4 10 9 HT7500ET 35 4 10 6 Max Min Charge Charge Current A Current A Battery Type Using minimum charge current will extend recharge time and increase risk of battery being undercharged ...

Страница 10: ...________________________________________________ Readings should be taken at installation and annually thereafter _________________________________________________________________________________ 1 41 81 121 161 201 2 42 82 122 162 202 3 43 83 123 163 203 4 44 84 124 164 204 5 45 85 125 165 205 6 46 86 126 166 206 7 47 87 127 167 207 8 48 88 128 168 208 9 49 89 129 169 209 10 50 90 130 170 210 11 ...

Страница 11: ...P a g e I n t e n t i o n a l l y B l a n k ...

Страница 12: ...oduced electronically or mechanically without written permission from the company E P M Form No 2100 11 21 2021 by EPM Printed in U S A East Penn Manufacturing Co Lyon Station PA 19536 0147 Phone 610 682 3263 Fax 610 682 4781 www dekabatteries com e mail reservepowersales dekabatteries com ...