4. Hardware
4.1 Board slot positions
The unit housing is divided into board slot positions. This means that the unit consists of a number of printed
circuit boards (PCBs) mounted in numbered slots. The green terminal blocks are then mounted in the PCBs.
Some of these board slots are standard and some are intended for options. The board slot positions are ar-
ranged as illustrated below.
Slot type
Option
Slot #1
Slot #3
Slot #5
Slot #7
Terminals
1-28
37-64
73-89
98-125
Power supply
Standard
X
AC measurements
Standard
X
Engine interface
Standard
X
Load sharing
G3
X
Power management
G4/G5/G8
X
Engine communication
H7
X
I/O extension
M12
X
Slot type
Option
Slot #2
Slot #4
Slot #6
Slot #8
Terminals
29-34
65-72
90-97
126-133
Analogue controller outputs
E1/E2
X
Analogue transducer outputs
F1
X
Combination outputs
EF2/EF4/EF5/EF6
X
Serial communication
H2/H3/H8.2
X
Engine communication
H5/H6
X
I/O extension cards
M13.2
X
I/O extension cards
M13.6/M14.6/M15
X
I/O extension cards
M13.8/M14.8/H8.8
X
Plant management
G7
X
Only hardware options, which will affect the hardware of the unit, are represented in the table.
The software options will be seen through the PC utility software. The software options that are
not represented in the above table can be found in the data sheet.
AGC-3 installation instructions 4189340728
UK
Hardware
DEIF A/S
Page 15 of 65
Содержание AGC-3
Страница 19: ...Mains unit AGC 3 installation instructions 4189340728 UK Hardware DEIF A S Page 19 of 65...
Страница 21: ...BTB unit AGC 3 installation instructions 4189340728 UK Hardware DEIF A S Page 21 of 65...
Страница 41: ...5 1 6 Single phase AGC 3 installation instructions 4189340728 UK Wirings DEIF A S Page 41 of 65...
Страница 42: ...5 1 7 2 phase L1L2 AGC 3 installation instructions 4189340728 UK Wirings DEIF A S Page 42 of 65...
Страница 43: ...5 1 8 2 phase L1L3 split phase AGC 3 installation instructions 4189340728 UK Wirings DEIF A S Page 43 of 65...