External set points (option G3)
The set point inputs are passive, in other words, an external power source is needed. This can be an active
output, for example from a PLC, or a potentiometer can be used.
0 to 10 V DC input using potentiometer
Multi-line 2
40 or 42
41 (Common)
10V DC
0V DC
Ø
Ø
2000 Ohm
¼ W
potentiometer
+/-10 V DC input using potentiometer
Multi-line 2
40 or 42
41 (Common)
10V DC
-10V DC
Ø
Ø
2000 Ohm
¼ W
potentiometer
0V DC
Ø
5.2.4 Multi-inputs
The multi-inputs are placed in slot #7, the terminal numbers for the individual multi-inputs can be seen in the
"Input/output list".
0(4) to 20 mA
Active transducer
0V DC
Multi-line 2
Multi-input
+12/24V DC
+
-
4-20 mA
transducer
Measurement
A
B
C
In
- Out
+ Out
AGC-3 installation instructions 4189340728
UK
Wirings
DEIF A/S
Page 50 of 65