The following has to be particularly taken into consideration:
■
The black surface of
HVI
®
Conductor
has to be cleaned prior to the installation of the EB
connection element. The surface must be smooth and free of grease. Potential grease layers
have to be removed with a cloth soaked with a special cleaning agent (Part No. 297 199).
■
The EB connection element shall not be dirty.
■
The screw of the EB connection element has to be tightened with a torque of 10 Nm.
■
The EB connection element has to firmly enclose the
HVI
®
Conductor
.
■
When using the
HVI
®
Conductor
with grey sheath, e.g. Part No. 819 025, this sheath has to
be removed for contacting the black semi-conductive coating underneath it. The black coating
shall not be cut in.
Additional mechanical fixing within the range of the second sealing end of the
HVI
®
Conductor
is
only permissible, if the calculated separation distance "s" is
≤
0.5 m (in air), while the following has
to be considered:
– The HVI® Conductor has to be fixed with a conductor holder, e.g. Part No. 275 220 / 275 225,
in combination with Part No. 106 760 (wall mounting) or spacer with conductor holder,
e.g. Part No. 106 812 / 106 813 (made of GRP and plastic).
– Fixing of conductor holders is only permissible in range a up to
≤
0.5 m, measured from the
head piece (see Figure 6 and Figure 7, page 10).
Figure 6
Connection of the
HVI
®
Conductor II / III
to an "isolated ring conductor"
sealing end range
spacer
e.g. Part No. 106 170
isolated ring conductor
head piece /
connection element
spacer
e.g. Part No. 106 812,
Part No. 106 813
(material GRP /
plastic)
Connection to the equipotential
bonding of the building
*
separation distance s
≤
0.5 m (in air)