6
Tabelle 1
Note:
When installing the concrete bases, make sure that the braces and the concrete recess in the con-
crete bases are flush. This ensures maximum stability of the tripod with air-termination tip when
driving in the fixing wedges (see Fig. 3, page 7 and Fig. 5, page 9).
In order to additionally protect roof sheeting, it is recommended to use support plates (Part. No. 102
050) to install the concrete bases (see Fig. 3, page 7).
GRP/Al supporting tube for HVI
®
long Conductors (Part No. 105 330) with tripod (Part No. 105 351)
GRP/StSt supporting tube for HVI
®
long Conductors (Part No. 105 314) with tripod (Part No. 105 351)
Description of the
Concrete base (17 kg)
Brace length/radius of
HVI
®
long Conductor
per brace
the tripod
1 x HVI
®
long Conductor
3 bases
r = 620 mm
Ø 20,23, installed inside
at least 2 Sockel bases underneath the brace
the supporting tube
1 base above the brace
1 x HVI
®
long Conductor
4 bases
r = 620 mm
Ø 20,23, installed outside
at least 2 Sockel bases underneath the brace
the supporting tube
2 bases above the brace
2 x HVI
®
long Conductor
4 bases
r = 620 mm
Ø 20,23, installed outside
at least 2 Sockel bases underneath the brace
the supporting tube
2 bases above the brace
3 x HVI
®
long Conductor
4 bases
r = 620 mm
Ø 20,23, installed outside
at least 2 Sockel bases underneath the brace
the supporting tube
2 bases above the brace
3 x HVI
®
long Conductor
4 bases
r = 620 mm
Ø 20,23,installed outside
at least 2 Sockel bases underneath the brace
the supporting tube
2 bases above the brace
Stützrohr für HVI®power Conductor Part No. 105 320 GRP NIRO
mit Dreibeinstaiv Part No. 105 351
Description of the
Concrete base (17 kg)
Brace length/radius of
HVI
®
long Conductor
per brace
the tripod
1 x HVI
®
power Conductor
3 bases
r = 620 mm
Ø 27, installed inside
3 bases underneath the brace
the supporting tube
1 x HVI
®
power Conductor
4 Sockel
r = 620 mm
Ø 27, installed outside
3 bases underneath the brace
the supporting tube
1 base above the brace
Minimum bending r
adius
HVI
®
long Conductor
-Conductor Ø 20 mm
⇒
at least 200 mm
-Conductor
Ø 23 mm
⇒
at least 230 mm
Minimum bending r
adius
HVI
®
power Conductor
-Conductor
Ø 27 mm
⇒
at least 270 mm
Table 2