![Deekax TALTERI DIVK-C 60 CD Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/deekax/talteri-divk-c-60-cd/talteri-divk-c-60-cd_installation-and-user-manual_2463012010.webp)
10
The fastening screws of the preheater
REMOVING THE FAN
The fans can be removed for cleaning or replacement.
Before removing the fans ,the heat recovery ventilation unit must be
disconnected from the power supply
When removing the extract air fan ,remove first the pre-heater housing by
unscrewing the upper fastening screw and removing the lower lower fastening screw(see the picture).
When removing the supply airfan, move first the reset button of the overheat protection
aside by removing the metal plate.
Unplug the fan plug connector.
Remove the fastening screws of the fan and
pull the fan out of the machine.
REMOVING OF THE ELECTRICAL HOUSING
The screws of the
bypass damper.
The screws of the
electrical housing.
The electrical housing can be removed for the necessary maintenance, the external controls
or the modbus termination by removing the bypass damper and then unscrewing the electrical
housing screws.