Mounting with the ceiling mounting plate(optional)

 

 
In  case  of  installation  of  HRV  to  the  ceiling,  ducts  can  be  installed  in  advance  and  secured  with  special 
supporting components.  Ceiling finishing works can be done before final installation of HRV. 
The  ceiling    mounting  bracket  is  usually  fastened  to  the  ceiling  with  four  8  mm  threaded  rods.  Sound-
absorbing rubber gaskets should be used with the threaded rods for sound  and vibration dampening. One 
of  advantages  of such  threaded rod  installation is  prevention  of sound  propagation  to  ceiling.  However,  if 
necessary, ceiling mounting bracket can be also connected directly to the ceiling. 
While  installing  the  HRV  drainage  of  the  condensate  should  be  taken  into  account:  the  HRV  should  be 
reclined slightly backwards. The backside of the HRV bottom  must  be at least two millimeters lower than its 
front side. 
 

Steam barrier installation

 

When installing a steam barrier it is advisable to use the ceiling mounting bracket as an aid. Size of holes 
punched in the steam barrier tape should be little smaller than  the  diameter of the  duct holes on the  ceiling 
mounting plate. 
When lifting up the ceiling mounting plate to it’s  place, press the steam  barrier tape  against the top surface 
of the mounting plate and use adhesive tape if necessary to ensure tight installation. 
The steam  barrier plastic tape can be sealed carefully to  the edges of the  mounting plate with adhesive 
tape. 
'FAIR' HRV are  also available with a rubber plate which makes sealing of the steam barrier easier. 
 

Liftning up the unit 

 

1. Set the cellular  plastic rings around the outlet ducts. 
Prior  to  installation  the  heat  exchanger  can  be 
demounted from the HRV in order to reduce the weight  
and  make the installation easier. Additionally, the HRV 
door can be removed  as well by removing the hex m6 
bolt from the bottom hinge. 

 

2.  Lift  the  HRV  carefully  towards  the  ceiling  mounting 
plate.  Align  the  hooks  placed  on  the  side  of  the  HRV 
towards the slots  on the ceiling mounting plate. Lift HRV  
upwards till the  hooks lock up to their first position. 
 
3.    Make  sure  that  the  cellular  plastic  rings  have 
remained on their places after the installation  and the 
electrical  wiring passes freely, and there are not extra 
objects inside the  unit. 
 
4. Applying more force lift the unit  up in order to lock up 
the both hooks of the HRV. 
 
5.    Make  sure  that  the  cellular  plastic  rings  are  tightly 
fastened against the ceiling mounting plate and lock the 
fastening with the two screws supplied. 
 
6. Make sure  that the HRV is declined enough in order 
to lead the condensing water out of the unit.

 

 

 
Attention! For the right handed model( FAIR 80 R) the ducts are located as mirror image. 
 
 
 
 
 

Electrica

cable 

pass-
through 

Locking  with 
two 

screws 

after 

the 

installation 

Fasting 
points  for  the 
ceiling 
mounting 

The 

cellular 

plastic  rings  are 
set around the air 
ducts. 

The  hooks  for  the 
ceiling mounting plate 

Picture 6: ceiling  mounting. (FAIR -80 L) 
 

Содержание FAIR-80 EC

Страница 1: ...it with fresh and clean air Humidity and impurities are exhausted through the thermal recovery unit that cost effectively heats the filtered ambient air Fresh warm air is channeled draught proof and noise free into the premises in necessary quantities ENSURE THE QALITY OF AIR EXCHANGE QUALITY CONTROLLED HEAT RECOVERY VENTILATOR FAIR 80 EC INSTALLATION AND USER MANUAL ...

Страница 2: ... 125 6 Fresh air intake from outdoors Ø125 7 Fresh air supply to the rooms Ø125 MACHINE PARTS AND TECHNICAL DATA Duct connections 4 pcs outer connection Ø 125mm 1 Supply fan EC 119 W 2 Exhaust fan EC 119 W 3 Rotating heat exchanger 4 Adjustable post heating element 800W 5 Exhaust air filter G4 6 Supply air filter G7 7 Drain in the bottom 1 4 internal thread 8 Control panel Total power consumption ...

Страница 3: ...f Finland are freely available on the Ministry of Environment website http www ym fi en US Space sufficient to open an HRV door should be taken into account when planning suitable place for HRV installation The electric socket should be located near the HRV device to make electricity connection conveniently available 1 2 Isolation of ducts Example of different types of insulation 1 An extract air ...

Страница 4: ... and whether the chosen wall is load bearing 2 Lift and set the device on the lower mounting brackets this will also facilitate the installation process 3 Fasten the upper mounting screws note the structure of the wall differs for load bearing and non bearing walls as noted above Mounted HRV should be slightly reclined backwards to ensure drainage of possible condensed water The rear side of the H...

Страница 5: ...led carefully to the edges of the mounting plate with adhesive tape FAIR HRV are also available with a rubber plate which makes sealing of the steam barrier easier Liftning up the unit 1 Set the cellular plastic rings around the outlet ducts Prior to installation the heat exchanger can be demounted from the HRV in order to reduce the weight and make the installation easier Additionally the HRV doo...

Страница 6: ...m When the HRV maintenance work is done it should be checked that there is enough water in the water trap Add more water if needed 1 6 Introduction Before using the machine make sure that the device is installed according to these instructions and connected to the ductwork according to HVAC plan the filters are in their places and there are no extra items inside the device the control panel is con...

Страница 7: ...7 ...

Страница 8: ...8 ...

Страница 9: ...ow and increase the noise level 1 Unit s status 2 Fan speed 3 Search menu 4 Fan speed selection 5 Selection of the value 6 Return 7 Alarm light 2 2 Basic functions of the control system After the HRV is connected to the electricity circuit the exhaust fan starts operating at the normal speed and the heat exchanger works normally During startup text Start is shown on the display in the speed data s...

Страница 10: ...e locked and a lock symbol will be shown on the display The key lock is released by pressing the same buttons and holding them for 2 seconds until the lock symbol disappears After heating Ventilation unit FAIR 80 has an 800 W electric post heating element which heats the supply air if needed When this function is activated the air temperature is regulated as precise as possible according to the se...

Страница 11: ...ng function immediately after the fireplace mode is turned off and the HRV has returned to its normal mode However if the Fireplace function is activated the defrosting function cannot be activated 2 3 Accessories HRV can be controlled with the following external transmitters and switches supplied as an extra equipment CO2 Control The device can be controlled based on the external CO2 transmitter ...

Страница 12: ...rvice menu during initial installation and configuration phase Remote control of supply air temperature The supply air temperature is controlled with B2 input 0 10v as follows 0 V 1 99 V Controlled with the panel 2 V 2 99 V 13 C 3 V 3 99 V 14 C 4 V 4 99 V 15 C 5 V 5 99 V 16 C 6 V 6 99 V 17 C 7 V 7 99 V 18 C 8 V 8 99 V 19 C 9 V 10 V 20 C When the remote control function is selected it overrides all...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...prior to making voltage tests taking insulation measurements other measurements or prior to performing any electrical engineering works which could cause damage of the HRV sensitive electronic units 3 2 Service program Fair ventilation unit has filters for supply and exhaust air The supply air filter is cassette type fine filter of the class F7 the exhaust filter is basic filter of the class G4 To...

Страница 16: ...2 Open the HRV door by using flat head screwdriver 3 Disconnect the electricity connectors of the exhaust fan from the right side of the heat exchanger case Coming from above wires could remain hanging 4 Disconnect the electricity connectors 5 pieces and sensors 2 pieces 5 Carefully pull out the heat exchanger case from the HRV simultaneously checking with the hand that there is enough room for th...

Страница 17: ...than usual Possible cause Remedy HRV settings are not configured properly Consult competent technician to configure settings of your HRV Clogged filters Change the filters Fan speed is too low Choose higher fan speed or adjust the fan speed settings through the service menu The air intake grille is clogged Check and clean the grille The fan wings are dirty Clean the fan wings Noise level is higher...

Страница 18: ...perature of T3 Sensor is above 50 C 2s X Cold exhaust air Temperature of T3 Sensor is below 14 C 5 min X Exhaust fan malfunction Requested speed is conflicting with exhaust fan settings 30 s X Hot supply air Temperature of T2 Sensor is above 55 C 2 s X Cold supply air Temperature of T2 Sensor is below 10 C 5 min X Air supply fan malfunction Requested speed is conflicting with air supply fan settin...

Страница 19: ...e a key point To place this text box anywhere on the page just drag it Condensate drain in the bottom 1 4 internal thread Condensate drain in the bottom 1 4 internal thread 1 SUPPLY AIR 2 EXTRACT AIR 3 OUTDOOR AIR 4 EXHAUST AIR Electric cable pass through Electric cable pass through 4 Specifications ...

Страница 20: ... power 119 W 2 pcs Drain Located in the bottom of HRV connection built in hose Maximum airflow 90 l s exhaust 85 l s supply air pressure loss of 50 Pa in both streams 5 Equipment 5 1 Standard Equipment Supply air filter F7 Exhaust air Filter G4 Post heating element Fair 80 800 W Intelligent multi function electronic user interface control box can be mounted onto the wall 20m cable included highly ...

Страница 21: ...21 ...

Отзывы: