1. Installation

 

 

1.1 General installation instructions

 

Heat Recovery Ventilator 'Fair' (here in after 

– HRV) should be installed in a warm  premises, with indoor 

temperature over  +5 °C.Ventilation ducts should be spacious enough so that the velocity of air streams is 
sufficiently low. The duct size is to be determined according to  the size of  the ventilated apartment and   the 
forecasted air consumption.  
 
National  Building  Code  of  Finland  (chapter  D2)  contain  regulations  and  guidelines  for  indoor  climate  and 
ventilation of buildings, airflow  planning and ducts recommendations, and terminal design and placement. 
Chapter C2 of the above mentioned National Building Code contains regulations and guidelines for moisture 
technical  planning.  National  Building  Code  of  Finland  are  freely  available  on  the  Ministry  of  Environment 
website (

http://www.ym.fi/en-US

). 

 
 Space sufficient to open an HRV door should be taken into account when planning suitable place for HRV 
installation.  The  electric  socket  should  be  located  near    the  HRV  device    to  make    electricity  connection  
conveniently available. 
 

1.2 Isolation of  ducts

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Example of different types of insulation: 
1. An extract air duct in the warm premises. 
2. A supply air duct from HRV to the valve. 
3.An exhaust  and outdoor air ducts installed indoors (warm space). 
4. An extract air duct  inside the insulation material of the room's ceiling installed above  the  vapor barrier 
5. and 6.  any type of duct installed in the cold space(e.g. in the attic) 
 

Note!

  Outdoor or exhaust  air ducts shall not be installed on the vapor barrier directly, but must be insulated 

with not less than 100 mm thick insulation material. 
 
 
 

Vaporproof  
outer surface 

Vaporproof  
outer surface 

Picture 4:isolation of ducts 

Содержание FAIR-80 EC

Страница 1: ...it with fresh and clean air Humidity and impurities are exhausted through the thermal recovery unit that cost effectively heats the filtered ambient air Fresh warm air is channeled draught proof and noise free into the premises in necessary quantities ENSURE THE QALITY OF AIR EXCHANGE QUALITY CONTROLLED HEAT RECOVERY VENTILATOR FAIR 80 EC INSTALLATION AND USER MANUAL ...

Страница 2: ... 125 6 Fresh air intake from outdoors Ø125 7 Fresh air supply to the rooms Ø125 MACHINE PARTS AND TECHNICAL DATA Duct connections 4 pcs outer connection Ø 125mm 1 Supply fan EC 119 W 2 Exhaust fan EC 119 W 3 Rotating heat exchanger 4 Adjustable post heating element 800W 5 Exhaust air filter G4 6 Supply air filter G7 7 Drain in the bottom 1 4 internal thread 8 Control panel Total power consumption ...

Страница 3: ...f Finland are freely available on the Ministry of Environment website http www ym fi en US Space sufficient to open an HRV door should be taken into account when planning suitable place for HRV installation The electric socket should be located near the HRV device to make electricity connection conveniently available 1 2 Isolation of ducts Example of different types of insulation 1 An extract air ...

Страница 4: ... and whether the chosen wall is load bearing 2 Lift and set the device on the lower mounting brackets this will also facilitate the installation process 3 Fasten the upper mounting screws note the structure of the wall differs for load bearing and non bearing walls as noted above Mounted HRV should be slightly reclined backwards to ensure drainage of possible condensed water The rear side of the H...

Страница 5: ...led carefully to the edges of the mounting plate with adhesive tape FAIR HRV are also available with a rubber plate which makes sealing of the steam barrier easier Liftning up the unit 1 Set the cellular plastic rings around the outlet ducts Prior to installation the heat exchanger can be demounted from the HRV in order to reduce the weight and make the installation easier Additionally the HRV doo...

Страница 6: ...m When the HRV maintenance work is done it should be checked that there is enough water in the water trap Add more water if needed 1 6 Introduction Before using the machine make sure that the device is installed according to these instructions and connected to the ductwork according to HVAC plan the filters are in their places and there are no extra items inside the device the control panel is con...

Страница 7: ...7 ...

Страница 8: ...8 ...

Страница 9: ...ow and increase the noise level 1 Unit s status 2 Fan speed 3 Search menu 4 Fan speed selection 5 Selection of the value 6 Return 7 Alarm light 2 2 Basic functions of the control system After the HRV is connected to the electricity circuit the exhaust fan starts operating at the normal speed and the heat exchanger works normally During startup text Start is shown on the display in the speed data s...

Страница 10: ...e locked and a lock symbol will be shown on the display The key lock is released by pressing the same buttons and holding them for 2 seconds until the lock symbol disappears After heating Ventilation unit FAIR 80 has an 800 W electric post heating element which heats the supply air if needed When this function is activated the air temperature is regulated as precise as possible according to the se...

Страница 11: ...ng function immediately after the fireplace mode is turned off and the HRV has returned to its normal mode However if the Fireplace function is activated the defrosting function cannot be activated 2 3 Accessories HRV can be controlled with the following external transmitters and switches supplied as an extra equipment CO2 Control The device can be controlled based on the external CO2 transmitter ...

Страница 12: ...rvice menu during initial installation and configuration phase Remote control of supply air temperature The supply air temperature is controlled with B2 input 0 10v as follows 0 V 1 99 V Controlled with the panel 2 V 2 99 V 13 C 3 V 3 99 V 14 C 4 V 4 99 V 15 C 5 V 5 99 V 16 C 6 V 6 99 V 17 C 7 V 7 99 V 18 C 8 V 8 99 V 19 C 9 V 10 V 20 C When the remote control function is selected it overrides all...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...prior to making voltage tests taking insulation measurements other measurements or prior to performing any electrical engineering works which could cause damage of the HRV sensitive electronic units 3 2 Service program Fair ventilation unit has filters for supply and exhaust air The supply air filter is cassette type fine filter of the class F7 the exhaust filter is basic filter of the class G4 To...

Страница 16: ...2 Open the HRV door by using flat head screwdriver 3 Disconnect the electricity connectors of the exhaust fan from the right side of the heat exchanger case Coming from above wires could remain hanging 4 Disconnect the electricity connectors 5 pieces and sensors 2 pieces 5 Carefully pull out the heat exchanger case from the HRV simultaneously checking with the hand that there is enough room for th...

Страница 17: ...than usual Possible cause Remedy HRV settings are not configured properly Consult competent technician to configure settings of your HRV Clogged filters Change the filters Fan speed is too low Choose higher fan speed or adjust the fan speed settings through the service menu The air intake grille is clogged Check and clean the grille The fan wings are dirty Clean the fan wings Noise level is higher...

Страница 18: ...perature of T3 Sensor is above 50 C 2s X Cold exhaust air Temperature of T3 Sensor is below 14 C 5 min X Exhaust fan malfunction Requested speed is conflicting with exhaust fan settings 30 s X Hot supply air Temperature of T2 Sensor is above 55 C 2 s X Cold supply air Temperature of T2 Sensor is below 10 C 5 min X Air supply fan malfunction Requested speed is conflicting with air supply fan settin...

Страница 19: ...e a key point To place this text box anywhere on the page just drag it Condensate drain in the bottom 1 4 internal thread Condensate drain in the bottom 1 4 internal thread 1 SUPPLY AIR 2 EXTRACT AIR 3 OUTDOOR AIR 4 EXHAUST AIR Electric cable pass through Electric cable pass through 4 Specifications ...

Страница 20: ... power 119 W 2 pcs Drain Located in the bottom of HRV connection built in hose Maximum airflow 90 l s exhaust 85 l s supply air pressure loss of 50 Pa in both streams 5 Equipment 5 1 Standard Equipment Supply air filter F7 Exhaust air Filter G4 Post heating element Fair 80 800 W Intelligent multi function electronic user interface control box can be mounted onto the wall 20m cable included highly ...

Страница 21: ...21 ...

Отзывы: