MCR 24, 24/28 MI, 30/35 MI, 34/39 MI
Alarm
code
Description
Probable causes
Checks/Solution
E3
Control panel: faulty
Power supply cable:
faulty
Control panel: faulty
Power supply cable: faulty
Power supply cable badly
connected
Check the electrical connections.
E4
No flame detection
(After a prolonged
shutdown, up to 5
start-up attempts may
be made)
No spark from the electrode
- Check the ignition electrode (spacing of the electrodes), its connector and its
connection cable
- Check the positioning of the electrode (gap: 3.5 mm)
- Check the earth
Presence of a series of sparks
No flame detection
- First check that the gas valve is open, that the gas supply pressure is present, that
the gas conduit has been sufficiently bled, that the air/flue gas conduit is not blocked
and is not leaking, that the siphon is full and not blocked
- If you use a two-phase electrical grid, jumper must be removed
- Clean or replace the ignition electrodes
- The CO
2
level at full load and part load
Detection of a parasite flame
Ionisation error (<3
µ
A or >9
µ
A)
- Check the combustion and the stability of the flame,
- The CO
2
level at full load and part load
- Check the electrical connections, particularly the earth
- Clean or replace the ignition electrodes
- Check the positioning of the electrode (gap: 3.5 mm)
E5
Ionisation error
Poor setting: CO
2
- Check the CO
2
level in the gas valve unit
- Check the ignition electrode (spacing of the electrodes), its connector and its
connection cable
- Check the concentric combusted gas evacuation and combustive air inlet pipes
- Check the high speed gas circulation,
E6
Detection of a parasite
flame
Replace the control panel if it is faulty
E7
Water pressure in the
boiler:absence
Pump operation: Poor
The water level and/or pressure
are too low
Check the water pressure in the installation
Carry out a visual check for the presence of any water leaks
No circulation
Check that the boiler circulating pump is working. Insert a screwdriver into the slot in
the pump spindle and turn the spindle several times to the right and left. Check the
wiring. If the pump still does not work, it is faulty and must be changed.
Too much air
When the pump is switched off, vent the system
Bad pump wiring
Check the electrical connections