Tab.16 Central heating circuit data
C140
C140 – 45
C140 – 65
C140 – 90
Water content
l
5.2
7.1
10.1
Water operating pressure
min
bar
0.8
0.8
0.8
Water operating pressure (MOP)
max
bar
3.0
3.0
3.0
Water temperature
max
°C
110
110
110
Operating temperature range
°C
7–90
7–90
7–90
Pressure drop secondary circuit (ΔT = 20 K)
mWC
1.1
1.7
1.6
Maximum permitted temperature difference
max
°C
40
40
(1) with a maximum flow temperature of 80 °C
Tab.17 Electrical data
C140
C140 – 45
C140 – 65
C140 – 90
Supply voltage (AC)
V
220
220
220
Power consumption – full load
max
W
68
92
124
Power consumption - low load
max
W
17
25
24
Power consumption – standby
max
W
5
6
5
Electrical protection rating
IP
X4D
X4D
X4D
Fuses
Main
A
10
10
10
Tab.18 Other data
C140
C140 – 45
C140 – 65
C140 – 90
Total weight (empty)
kg
87
98
109
Appliance dimensions
Height x Width x Depth
mm
1340 x 600 x
605
1340 x 600 x
605
1562 x 600 x
605
Average acoustic level at a distance of one me
tre from the boiler
dB(A)
40
40
45
See
The back cover for contact details.
8 Technical specifications
30
DIEMATIC Evolution - C140