6.3.2
Hydraulic connection between the thermodynamic water
heater and an instant boiler
Example of hydraulic connection in HYBRID Mode
Fig.16
230V
50Hz
50
100
bar
4
3
2
1
0
°C
120
20
1204
ON
OFF
A
U
T
0
MW-5000495-1
1
2
1 Thermodynamic water heater
2 Instant boiler
6.3.3
Connecting the condensate discharge pipe
1. Insert the condensate collector hose (Ø 9 mm) into the discharge
opening.
Caution
Do not block the condensate discharge pipe.
Connect the condensate discharge pipe in accordance with
prevailing local standards.
Safety valve or safety unit
Caution
Germany: In accordance with the safety regulations, a safety
unit calibrated to 0.6 MPa (6 bar) must be fitted on the domestic
cold water inlet on the domestic hot water tank.
Belgium: In accordance with the safety regulations, a safety unit
calibrated to 0.7 MPa (7 bar), and approved by Belgaqua, must
be fitted on the domestic cold water inlet on the domestic hot
water tank.
Other countries: In accordance with the safety regulations, a
safety unit calibrated to 0.7 MPa (7 bar) must be fitted on the
domestic cold water inlet on the domestic hot water tank.
France: We recommend NF-marked hydraulic diaphragm safety units.
Integrate the safety valve in the cold water circuit.
6 Installation
7629886 - v07 - 20072020
ETWH
31