5
29/05/06 -300008885-001-A
BMR 80
2 Technical characteristics
3 Package list
BMR 80
Primary circuit (heating water)
Maximum operating temperature
°C
95
Maximum operating pressure
bar
10
Maximum operating pressure in accordance with W/TPW (3)
bar
6
Coil water capacity
l
3
Coil exchange surface
m
2
0.75
Secondary circuit (domestic water)
Maximum operating temperature
°C
95
Maximum operating pressure
bar
10
Maximum operating pressure in accordance with W/TPW (3)
bar
6
Water capacity
l
80
Performance
Power exchanged
(1)
kW
22.6
Continuous flow
(1)
l/h
555
Specific flow at
∆
T 30 K
(2)
l/min
16.5
Draw-off capacity
l/10 mm
165
Weigh
kg
49
(1)
Domestic cold water inlet: 10 °C - Domestic hot water outlet: 45 °C - Primary circuit
(heating water): 80 °C
(2)
Domestic cold water inlet: 10 °C - Domestic hot water outlet: 45 °C - Primary circuit
(heating water): 80 °C - DHW sensor temperature: 60 °C
(3)
Swiss Directives
Description
BMR 80
- Tank
EE 53
- Linking kit
HG 29
To be ordered separately
- NTC sensor
AD 226