Pressure reducer
If the mains pressure exceeds 80% of the valve or safety unit setpoint
(e.g.: 5.5 bar for a safety unit set at 7 bar), a pressure reducer must
be fitted upstream of the appliance. Install the pressure reducer
downstream the water meter in such a way as to ensure the same
pressure in all of the installation pipes.
n
Domestic hot water circulation loop
To guarantee the availability of hot water as soon as the taps are
turned on, a circulation loop between the draw-off points and the
recirculation pipes in the DHW tank can be installed. A non-return
valve must be included in this loop.
n
Measures to take to prevent hot water flow reversal
Fit a one-way valve to the domestic cold water circuit.
4.7
Electrical connections
4.7.1.
Recommendations
WARNING
Only qualified professionnals may carry out electrical
connections, always with the power off.