AWHP-2 MIV-3
AWHP 11 MR-2
AWHP 11 TR-2
AWHP 16 MR-2
AWHP 16 TR-2
Sound power level, indoors - outdoors
L
WA
dB (A)
53 - 69
53 - 69
Annual energy consumption under average conditions
Q
HE
kWh
GJ
3783
5184
Annual energy consumption under colder conditions
Q
HE
kWh
GJ
3804
5684
Annual energy consumption under warmer conditions
Q
HE
kWh
GJ
2580
4120
(1) The rated heat output
Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup
is equal to the supplementary capacity for heating
sup(Tj).
(2) If
Cdh is not determined by measurement, the default degradation coefficient is Cdh = 0.9.
3.2 Sensor characteristics
Tab.10 Outside temperature sensor
Temperature in °C
-20
-16
-12
-8
-4
0
4
8
12
16
20
24
Resistance in Ω
2392
2088
1811
1562
1342
1149
984
842
720
616
528
454
Tab.11 Domestic hot water sensor, flow sensor
Temperature in °C
0
10
20
25
30
40
50
60
70
80
90
Resistance in Ω
32014
19691
12474
10000
8080
5372
3661
2535
1794
1290
941
3 Technical specifications
16
AWHP-2 MIV-3
7611973 - v04 - 07032016