3 Technical specifications
3.1 Heat pump
Maximum operating pressure: 3 bar
Tab.3
Conditions of use
Water (°C)
Outside air (°C)
Limit operating temperatures in Heating
mode
+18 / +60
AWHP 4 MR, AWHP 6 MR-2 : -15 / +35
Other models: -20 / +35
Limit operating temperatures in Cooling
mode (MIV-3/EM, MIV-3/ET, MIV-3/H)
+18 / +25
+7 / +40
Limit operating temperatures in Cooling
mode (MIV-3/EMI, MIV-3/ETI, MIV-3/HI)
+7 / +25
+7 / +40
Tab.4
Heating mode: outside air tempe7°C, water temperature at the 35°C. Performances in accordance with
EN 14511-2.
Measurement type
Unit
AWHP
4 MR
AWHP 6
MR-2
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Heat output
kW
3.94
5.73
8.26
11.39
11.39
14.65
14.65
Coefficient of per
formance (COP)
4.53
4.04
4.27
4.65
4.65
4.22
4.22
Absorbed electrical
power
kWe
0.87
1.42
1.93
2.45
2.45
3.47
3.47
Nominal amperage
A
4.11
6.57
8.99
11.41
3.8
16.17
5.39
Nominal water flow
rate (ΔT = 5K)
m
3
/hour
0.68
0.99
1.42
1.96
1.96
2.53
2.53
Tab.5
Heating mode: outside air tempe2 °C, water temperature at the 35°C. Performances in accordance with
EN 14511-2.
Measurement
type
Unit
AWHP 4
MR
AWHP 6
MR-2
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Heat output
kW
3.76
3.65
5.30
10.19
10.19
12.90
12.90
Coefficient of
performance
(COP)
3.32
3.22
3.46
3.20
3.20
3.27
3.27
Absorbed elec
trical power
kWe
1.13
1.16
1.53
3.19
3.19
3.94
3.94
Tab.6
Cooling mode: outside air tempe35°C, water temperature at the 18°C. Performances in accordance with
EN 14511-2.
Measurement
type
Unit
AWHP 4
MR
AWHP 6
MR-2
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Cooling output kW
3.84
4.69
7.90
11.16
11.16
14.46
14.46
Energy efficien
cy ratio
4.83
4.09
3.99
4.75
4.75
3.96
3.96
Absorbed elec
trical power
kWe
0.72
1.15
2.00
2.35
2.35
3.65
3.65
Nominal am
perage
A
3.40
5.43
9.40
11.05
3.68
17.15
5.71
3 Technical specifications
12
AWHP-2 MIV-3