When one of the codes below is displayed, contact the professional 

responsible for maintenance of the heat pump.

Tab.23 List of blocking codes linked to the SCB-10 PCB

Code

Message

Description

H00.69

TbufferTankOpen

Buffer Tank temperature sensor is either removed or 

measures a temperature below range

H00.70

TbufferTankClosed

Buffer Tank temperature sensor is either shorted or measures 

a temperature above range

H00.71

TbufferTankTopOpen

Buffer Tank top temperature sensor is either removed or 

measures a temperature below range

H00.72

TbufferTankTopClosed

Buffer Tank top temperature sensor is either shorted or 

measures a temperature above range

H00.74

TBufferTankMissing

Buffer Tank temperature sensor was expected but not 

detected

H00.75

TBufferTankTop Miss

Buffer Tank Top temperature sensor was expected but not 

detected

H00.76

TcascadeFlow Open

Cascade Flow temperature sensor is either removed or 

measures a temperature below range

H00.77

TcascadeFlow Closed

Cascade Flow temperature sensor is either shorted or 

measures a temperature above range

H00.78

TcascadeFlow missing

Cascade Flow temperature sensor was expected but not 

detected

H02.02

Wait Config Number

Waiting For Configuration Number

H02.03

Conf Error

Configuration Error

H02.04

Parameter Error

Parameter Error

H02.05

CSU CU mismatch

CSU does not match CU type

H02.16

Int CSU Timeout

Internal CSU Timeout

H02.36

Funct device lost

Functional device has been disconnected

H02.40

Function unavailable

Function unavailable

H02.45

Full Can Conn Matrix

Full Can Connection Matrix

H02.46

Full Can Device Adm

Full Can Device Administration

H02.47

Failed Conn Funct Gr

Failed Connecting Function Groups

H02.48

Funct Gr Conf Fault

Function Group Configuration Fault

H02.49

Failed Init Node

Failed Initialising Node

H02.55

Inval or miss SerNR

Invalid or missing device serial number

H02.61

Unsupported function

Zone A doesn't support the selected function

H02.62

Unsupported function

Zone B doesn't support the selected function

H02.63

Unsupported function

Zone C doesn't support the selected function

H02.64

Unsupported function

Zone D doesn't support the selected function

H02.65

Unsupported function

Zone E doesn't support the selected function

H02.66

TAS not connected

The anti corrosion protection (TAS) of the Domestic Hot Water 

tank is not connected

H02.67

TAS short-circuit

The anti corrosion protection (TAS) of the Domestic Hot Water 

tank is shortend

H10.00

T Flow Zone A Open

Flow temperature sensor Zone A Open

H10.01

T Flow Zone A Closed

Flow temperature sensor Zone A Closed

H10.02

T Dhw Zone A Open

Domestic Hot Water temperature sensor Zone A Open

H10.03

T Dhw Zone A Closed

Domestic Hot Water temperature sensor Zone A Closed

H10.04

TSwimmPoolZoneA Open

Swimming Pool Temperature Sensor Zone A Open

H10.05

TSwimmPoolZoneAClose

Swimming Pool Temperature Sensor Zone A Closed

H10.09

T Flow Zone B Open

Flow temperature sensor Zone B Open

H10.10

T Flow Zone B Closed

Flow temperature sensor Zone B Closed

H10.11

T Dhw Zone B Open

Domestic Hot Water Temperature Sensor Zone B Open

H10.12

T Dhw Zone B Closed

Domestic Hot Water temperature sensor Zone B Closed

H10.13

TSwimmPoolZoneB Open

Swimming Pool Temperature Sensor Zone B Open

6  Troubleshooting

7684505 - v04 - 10022022

MIT-S

25

Содержание AWHP 11 MR-2

Страница 1: ...ADVANCE SUSTAINABLE COMFORT MW 1001233 1 MW 1001233 1 en User Guide Reversible air water Split Inverter heat pump HPI S MIT S 4 8 E MIT S 11 16 E MIT S 22 27 E MIT S 4 8 H MIT S 11 16 H MIT S 22 27 H...

Страница 2: ...17 4 6 1 Definition of the term zone 17 4 6 2 Changing the name and symbol of a zone 17 4 7 Personalising the activities 17 4 7 1 Definition of the term Activity 17 4 7 2 Changing the name of an activ...

Страница 3: ...ocedure 28 7 2 Disposal and recycling 29 8 Energy savings 29 9 Product fiche and package fiche 29 9 1 Compatible heating devices 29 9 2 Product fiche 29 9 3 Product fiche Temperature controller 31 9 4...

Страница 4: ...tandards Earth the appliance before making any electrical connections Type and calibre of the protective equipment refer to the Recommended cable cross sections chapter See the Installation and Servic...

Страница 5: ...nufacturer its after sales service or persons with similar qualifications in order to avoid danger When connecting the appliance to the electricity mains or carrying out any other wiring work refer to...

Страница 6: ...the system to leave the following functions running Anti blocking of pumps Frost protection Never remove or cover the labels and data plates affixed to appliances Labels and data plates must be legib...

Страница 7: ...ser If maintenance is necessary warn the user of the obligation to check the appliance and keep it in good working order Give all the instruction manuals to the user User s liability To guarantee opti...

Страница 8: ...in this manual must also be followed Supplements or subsequent regulations and guidelines that are valid at the time of installation shall apply to all regulations and guidelines specified in this man...

Страница 9: ...dance with EN 14511 2 Measurement type Unit AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 AWHP 11 MR 2 AWHP 11 TR 2 AWHP 16 MR 2 AWHP 16 TR 2 AWHP 22 TR 2 AWHP 27 TR 2 Heat output kW 3 47 3 74 5 93 10 19 10 19...

Страница 10: ...682 6 157 9 605 8 850 9 605 8 850 9 605 8 850 9 605 8 850 14 825 13 660 16 078 14 815 Refrigerant connec tion Liquid Gas inch 1 4 1 2 1 4 1 2 3 8 5 8 3 8 5 8 3 8 5 8 3 8 5 8 3 8 5 8 3 8 1 or 3 8 3 4...

Страница 11: ...h 1 0 1 0 1 0 Seasonal space heating energy efficiency under average conditions s 134 125 129 Seasonal space heating energy efficiency under colder conditions s 109 116 119 Seasonal space heating ener...

Страница 12: ...kW 4 7 Rated heat output under warmer conditions Prated kW 8 13 Declared capacity for heating for part load at an indoor temperature of 20 C and outdoor temperature Tj Tj 7 C Pdh kW 6 8 8 6 Tj 2 C Pdh...

Страница 13: ...ter No No Rated heat output under average conditions 1 Prated kW 11 14 Rated heat output under colder conditions Prated kW 12 14 Rated heat output under warmer conditions Prated kW 18 20 Declared capa...

Страница 14: ...for heating sup Tj 2 If Cdh is not determined by measurement the default degradation coefficient is Cdh 0 9 See The back cover for contact details 3 3 4 Circulating pump Important The benchmark for th...

Страница 15: ...es run each time the power is switched on 2 Check the hydraulic pressure in the installation indicated on the user interface Important Recommended hydraulic pressure between 1 5 and 2 0 bar 4 2 2 Shut...

Страница 16: ...ramme 4 5 Regional and ergonomic parameters You can personalise your appliance by modifying the parameters linked to your geographic location and the ergonomics of the user interface 1 Press the butto...

Страница 17: ...manual 4 7 Personalising the activities 4 7 1 Definition of the term Activity Activity this term is used when programming time ranges It refers to the client s desired comfort level for different act...

Страница 18: ...enables the room temperature to be modulated according to your needs and to optimise your energy consumption 1 Select the icon for the affected zone for example 2 Select the desired operating mode Tab...

Страница 19: ...day 3 Select the day to be modified 4 Carry out the following actions according to your needs Modify the timings for programmed activities Add a new activity Delete a programmed activity choose the a...

Страница 20: ...ration DHW Schedule 5 Select the programme to be modified The programmed activities for Monday are displayed The last activity of the day remains active until the first activity of the following day 6...

Страница 21: ...ith a leak tightness check in accordance with prevailing standards is obligatory Maintenance operations are important for the following reasons To guarantee optimum performance To extend the life of t...

Страница 22: ...The setting for the safety thermostats 5 3 Maintenance message When a maintenance operation is required your appliance will alert you in two ways A maintenance message will appear on the screen The M...

Страница 23: ...ayed again contact the installer 6 1 1 Types of error code The user interface can display three types of error code Tab 21 Type of code Code format Colour of the status LED Warning Axx xx Green flashi...

Страница 24: ...l unit PCB terminal block open H02 10 Full Block Full blocking of the device recognized BL input on the central unit PCB terminal block open H02 23 System flow error System water flow error active Flo...

Страница 25: ...n Connection Matrix H02 46 Full Can Device Adm Full Can Device Administration H02 47 Failed Conn Funct Gr Failed Connecting Function Groups H02 48 Funct Gr Conf Fault Function Group Configuration Faul...

Страница 26: ...the professional responsible for maintenance of the heat pump Tab 24 List of lockout codes Code Message Description E00 00 TFlow Open Flow temperature sensor is either removed or measures a temperatur...

Страница 27: ...OBD Error Object Dictionary Error A02 37 Uncritic device lost Uncritical device has been disconnected A10 45 RoomTempZoneA miss Measure of Room Temperature Zone A is missing A10 46 RoomTempZoneB miss...

Страница 28: ...not op erating Check that the heat pump is switched on Check the fuses and switches on the electrical installation The water pressure is too low 1 bar Top up the system with water An error code appear...

Страница 29: ...ath consumes twice as much water and energy 9 Product fiche and package fiche 9 1 Compatible heating devices Tab 28 Outdoor unit Associated compatible indoor units AWHP 4 5 MR MIT S 4 8 E MIT S 4 8 H...

Страница 30: ...1 51 51 Rated heat output under colder warmer climate condi tions kW 4 8 4 8 7 13 7 13 Seasonal space heating energy efficiency under colder warmer climate conditions 113 167 113 167 113 161 113 161 A...

Страница 31: ...energy efficiency 2 9 4 Package fiche Medium temperature heat pumps Important Medium temperature application means an application where the heat pump space heater or heat pump combination heater deliv...

Страница 32: ...I 1 5 Class IV 2 Class V 3 Class VI 4 Class VII 3 5 Class VIII 5 Temperature control Seasonal space heating energy efficiency of heat pump 1 If tank rating is above A use 0 95 from fiche of boiler fro...

Страница 33: ...ge 136 127 131 Tab 35 Package efficiency Un it AWHP 11 MR 2 AWHP 11 TR 2 AWHP 16 MR 2 AWHP 16 TR 2 AWHP 22 TR 2 AWHP 27 TR 2 Seasonal space heating energy efficiency of package 127 127 123 123 116 114...

Страница 34: ...es Factory set name Factory set tempera ture Name and temperature defined by the customer Activity 1 Sleep 30 C Activity 2 Home 25 C Activity 3 Away 25 C Activity 4 Morning 25 C Activity 5 Evening 25...

Страница 35: ...hnological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent i...

Страница 36: ...46 801 080 881 Infocentrala NEUBERG S A LU DE DIETRICH SERVICE AT DE DIETRICH CN www neuberg lu www dedietrich heating com www dedietrich heiztechnik com 352 0 2 401 401 0800 201608 freecall 39 rue Ja...

Отзывы: