Operating instructions

 

Version 1.0 

2018/03/17 

page 7 of 24 

 

$--ALA,084410.00,FR,OT,11,910,H,V,FN power batt      *36 

-  fault with battery defect 

$--ALA,084720.00,FR,OT,11,910,H,V,FN module FM 4   *2A 

-  fault with a missing 

 

  module (FM01) 

1.11. 

Main panel AHT01-E 

The AFMS can be operated from the main panel (AHT) and also from an additionally connected main 
panel (HT). There must always be at least one main panel (AHT as principal) in an AFMS! In addition 
to the main panel (AHT as principal), additional panels (main panel [HT] and main panels [AHT]) can 
be used in parallel. The operating possibilities are considerably reduced on all parallel-operated main 
panels, whether HT or AHT. 

The operation of the main panel (AHT) is based on the operation of the main panel (HT) and is similar 
to it. Nonetheless, the main panel (AHT) offers more comfortable operation and operator guidance 
thanks to its larger display and an additional internal memory.  

The main panel (AHT) is normally installed in a bridge control console on the command bridge near to 
the other modules.  

The main panel (AHT) consists of a large graphic display, 19 keys, 7 illuminated display fields (3-
coloured red-yellow-green) and an acoustic sounder. In order to be able to adapt the illuminated 
display fields optimally to the local conditions, the light intensity can be adjusted. The contrast and the 
brightness of the background lighting can also be adjusted (day/night operation).  

1.12. 

Main panel HT01-E 

The AFMS can be operated through the main panel (AHT) and the main panel (HT). There must 
always be at least one main panel (AHT) in an AFMS (as master).  

The main panel (HT) in parallel operation is normally installed in the MCR (machine control room) or 
another safety station. On river ships, installation is also possible in the reception or on the bridge, as 
well as other installations in firefighting locations.  

The main panel (HT) consists of a display (2 rows each with 20 characters), 10 keys with the 
associated multi-coloured illuminated fields, 2 further LEDs (with illuminated display fields) and an 
acoustic sounder. All illuminated display fields, the display and the LEDs can also be adjusted for 
brightness (as above), which also applies for the contrast of the LCD display. 

A maximum of 2 main panels (HT) can be connected to an AFMS in addition to one main panel (AHT). 
The connected main panels (HT) always run only parallel to an AFMS and this restricts their function. 
The operation of a main panel (HT) is in the operating instructions of the MED-approved FMS3000, 
which in this case is included in the delivery. 

1.13. 

Data module DT01-E 

The data module is intended for saving the configuration data of the AFMS and data created during its 
operation on a special SD card. For this purpose, the module has its own microcontroller for reading 
and writing onto the SD card. Operation is thus ensured independently of superior systems. The 
module is connected through its own interface. 

On the back of the module is a small slot for such card. It locks into position after insertion it into the 
card holder. In order to remove the SD card, it must be first ‘pressed’ a little – the card unlatches, 
comes out slightly and can then be removed easily. 

Содержание 20140208BA

Страница 1: ... 4 7 2 3 5 6 8 9 0 A A A Version history Version Date Author Checked Notes 0 5 10 23 09 09 STO FWU commissioning 0 5 11 28 06 11 TF TM revised 0 6 05 02 14 JB TK layout revised terms adapted 0 7 07 02 14 JB TK revised 0 8 08 02 14 TK STO revised and further errors corrected 0 9 21 04 16 TK STO Improved information to earth fault measurements 1 4 1 0 18 03 17 TK STO Information about the system s f...

Страница 2: ...evels 8 2 5 1 Access level 1 8 2 5 2 Access level 2 8 2 5 3 Access level 3 8 2 5 4 Access level 4 8 2 6 Display and operating elements of the panel AHT 8 2 6 1 Graphic display 10 2 6 2 Menu keys soft keys 10 2 6 3 Number block 11 2 6 4 HOME and BACK keys 11 2 6 5 FIRE SILENCE FAULT SILENCE and RESET keys 12 2 6 6 FIRE FAULT and RESET illuminated fields 12 2 6 7 ALARM IN SEQU illuminated field 13 2...

Страница 3: ...zones or outputs 18 2 8 12 Set delay times of the detectors 18 2 8 13 Set thresholds for detectors 18 2 8 14 Overview display status of the detectors 18 2 8 15 Activate deactivate loops 18 2 9 Main panel in parallel operation 18 3 Glossary 19 3 1 Acoustic sounder 19 3 2 Fire detector 19 3 3 Fire zone 19 3 4 Graphic display 19 3 5 Configuration Config Tool 19 3 6 LED 20 3 7 Loop 20 3 8 Illuminated ...

Страница 4: ... of the fire loop module Independent of the configuration the main module transmits to the output module which outputs it should now connect It also sends this alarm to the VDR module and the printer module if present The VDR and printer modules output the fire alarm through a VDR output or printer respectively In addition the main panel warns the user acoustically and optically of the event fire ...

Страница 5: ...r transitions from deck to deck are to be observed Each loop consists of two equivalent connection pairs Drive Return A three core wire is connected to connectors The data transmission and electricity supply of the fire detectors is run through this wire All fire detectors are parallel connected to this wire The detector loops are monitored for short circuit cable breakage and earth connection so ...

Страница 6: ... exceed 1 6A Is the total current exceeded the microcontroller switches off the loop with the highest current The module in addition to the connections for the fire detectors also contains 8 potential free outputs which can be configured as required for fault or fire Two microcontrollers control and monitor the loops their outputs and communicate with the BUS 1 9 Printer module DM01 E The printer ...

Страница 7: ...eration 1 12 Main panel HT01 E The AFMS can be operated through the main panel AHT and the main panel HT There must always be at least one main panel AHT in an AFMS as master The main panel HT in parallel operation is normally installed in the MCR machine control room or another safety station On river ships installation is also possible in the reception or on the bridge as well as other installat...

Страница 8: ...y knowledge of the AFMS by simply pressing a key and or calling up on screen 2 5 2 Access level 2 Level 2 is directly accessible without having to open anything and without using tools Level 2 can only be activated with knowledge of the AFMS and not by randomly pressing a key It is possible to call up menus at this level some of which are protected by a password 2 5 3 Access level 3 The AFMS is lo...

Страница 9: ...E ALARM TEST MODE 1 FIREALARMSYSTEM AFMS 3000 4 7 2 3 5 6 8 9 0 A A A The Menus for the various functions are structured in a strict hierarchy starting from a main menu display without operation system runs without messages It is thus possible to select the relevant functions of the system by navigating forwards and backwards Graphic display Number block HOME key BACK key Soft keys FIRE and A key ...

Страница 10: ...play In the menu field only the current menu entry is shown Additional information is also displayed such as the number of new and accepted fire alarms or faults soft keys In the actions field certain elements of the menu navigation or an action are shown In the four soft key menu fields with surrounds the functions of the directly subordinate menu are shown 2 6 2 Menu keys soft keys Menu fields A...

Страница 11: ...cal display for menu navigation The function of each key is shown in the graphical field directly above the relevant key menu field 2 6 3 Number block An extra number block with numbers 0 9 is available for the input of parameters or numerical values such as date or sensitivities of individual detectors 2 6 4 HOME and BACK keys The Home key can be used to return directly to the main menu The Back ...

Страница 12: ...h as a fire alarm or a fault FIRE A o press 1st key switch off signal silence o press 2nd key accept fire alarm or o press 2nd key open fire menu required for a RESET FAULT A o press 1st key switch off signal silence o press 2nd key accept fault or o press 2nd key open fault menu required for a RESET RESET o Reset fire alarm or fault 2 6 6 FIRE FAULT and RESET illuminated fields FIRE FAULT RESET A...

Страница 13: ...l messages have been reset The RESET illuminated field can also turn from green to yellow for a short time During this time for example a system reset is being transmitted to a module and executed After a restart of the AFMS the RESET field blinks until all modules and assemblies are initialised also in case a previously switched off loop is reconnected 2 6 7 ALARM IN SEQU illuminated field ALARM ...

Страница 14: ...put of the output module automatically activates an externally connected automatic general alarm system The display then shows at top right corner general alarm If more than the five 5 fire alarms that can be displayed accumulate it is possible to change between the fire alarms by pressing the menu key The display is changed from fire alarm to a fault by pressing the relevant FIRE or FAULT key The...

Страница 15: ...an be shown it is possible to switch between the faults by pressing the menu key The display is switched from showing a fire alarm to a fault by pressing the FIRE A or FAULT A key The display always shows the newest and the oldest fire alarm and the newest and oldest fault for 30 s after the last interaction Resetting a fault must be undertaken out of the menu entry Accepted Fault repeated pressin...

Страница 16: ... functions are available 1 Reset with deleting all with password The previously accumulated fire alarms and faults will be all deleted and the system is restarted 2 Reset with hold all The system will be only restarted holds all data 3 Reset with new init modules with password All fire alarms and faults will be deleted the modules and detectors are newly initialised and the system is then restarte...

Страница 17: ... menu entry enables the brightness of the yellow and red LEDs to be adjusted It can be reached from the main menu by selecting the sub menu entries è Service è Settings è Dimmer LED TFT è Fault LED red yellow 2 8 9 Change password and or change display language The password has to be entered This menu entry enables the password and or the menu language to be changed It is necessary to know the old...

Страница 18: ...ire Alarm System è Management è Adjustments 2 8 14 Overview display status of the detectors This menu entry enables the status of all detectors to be displayed in a tabular overview The display shows all detectors in the currently selected loop selected using the number block It can be reached from the main menu by selecting the sub menu entries è Fire Alarm System è Management è Loop and key More...

Страница 19: ...also administrate addressable detectors sensors working with HOCHIKI ESP telegrams The AFMS is mainly designed to operate only with HOCHIKI ESP sensors Manual call points and also all address units different CHQ modules are possible are counted like other detectors The functional principle of a detector in the example a smoke detector is used is explained in little more detail in section 3 13 3 3 ...

Страница 20: ...pplies fail the AFMS switches to accumulator emergency operation until the accumulator has run down Then the system switches off protection against full discharge for the accumulator s 3 10 Loops Up to 16 conventional fire detectors can content a conventional loop in parallel In the last fire detector of a loop a termination resistor of 3kΩ 10 must be fitted With non addressable fire detectors whi...

Страница 21: ... on the existing air exchange to the detector s position Thus there may be rooms present where no air exchange takes place and the detector is constantly into this fog threshold which then inevitably lead into a technical error or a PRE ALARM condition This is here a normal function due to the present environment If a detector reports unusually often alarms his position is more than unfavorable A ...

Страница 22: ... 49 0 4105 65 60 0 DECKMA GmbH Fax 49 0 4105 65 60 25 Email info deckma gmbh de Internet www deckma gmbh de Operating instructions Version 1 0 2018 03 17 page 22 of 24 4 Menu structures 4 1 Menu Main Page Main Page AFMS3000 Firealarm System Service ...

Страница 23: ...entation 20140208BA AFMS3000 Tel 49 0 4105 65 60 0 DECKMA GmbH Fax 49 0 4105 65 60 25 Email info deckma gmbh de Internet www deckma gmbh de Operating instructions Version 1 0 2018 03 17 page 23 of 24 4 2 Menu Service ...

Страница 24: ...ion 20140208BA AFMS3000 Tel 49 0 4105 65 60 0 DECKMA GmbH Fax 49 0 4105 65 60 25 Email info deckma gmbh de Internet www deckma gmbh de Operating instructions Version 1 0 2018 03 17 page 24 of 24 4 3 Menu Fire Alarm System ...

Отзывы: