[2]  Auto-arm Control                 

Pressing [2] while in the User Function menu will enable (3 beeps) or disable (one long beep) the Auto-arm fea-
ture, by partition. With this feature enabled, the panel will automatically arm in the Away mode (Stay Away zones
active) at the same time each day.  The auto-arm time is programmed with the [

,

][6][Master Code][3] command.

[3]  Auto-arm Time                     

The system can be programmed to arm at a programmed time each day, per partition.  

Upon entry of this section, enter 4 digits for the 24-hour Auto-arm time for each day of the week.  

At the selected auto-arm time, the keypad buzzers will sound for a programmed amount of time (programmable
by the installer only) to warn that an auto-arm is in progress. The bell can also be programmed to squawk once
every 10 seconds during this warning period. When the warning period is complete, the system will arm with no
exit delay and in the Away Mode.

Auto-arming can be cancelled or postponed by entering a valid access code only, during the programmed warn-
ing period.  Auto-arming will be attempted at the same time the next day. When the auto-arming process is can-
celled or postponed, the Auto-arm Cancellation Reporting Code will be transmitted (if programmed).

If arming is inhibited by one of the following, the Auto-arm Cancellation transm ss on will be communicated.

- AC / DC Inhibit Arm

- Latching System Tampers

- Zone Expander Supervisory Fault

[4]  System Test                        

The system’s Bell Output (2s), Keypad Lights and Communicat r are tested. This test will also measure the panel’s
standby battery.

[5]  Enable DLS / Allow System Service  

If enabled, the installer will be able to access Installer Programming by DLS. In case of DLS access this provides a
window where rings will be detected by the panel  The DLS window will remain open for 6hrs, during which time
the installer will be able to enter DLS an unlimited number of times.  After the 6-hr window has expired, Installer’s
Programming will be unavailable again until the window is re-opened.  

[6]  User Call-up             

If enabled by the Installer, the pane  will make 1 attempt to call the downloading computer.  The downloading
computer must be waiting for the panel to call before downloading can be performed.

[7]  Music Input On/Off               

If enabled on the PC5936 Audio Interface Module, the user can turn Background Music on or off. 

[8]  User Walk Test (For Europe only)

This test allows the user to verify operation of system detectors and notifies the central station that a Walk Test is
in progress. 

Note: Fire zones, the 'F' key, and 2-wire Smoke detectors are excluded from this test. Violation of these zones will 
cause the system to exit the walk test then generate and transmit  alarm condition to the central station.

1. Press 

 to enable Walk Test. The system will notify the Central Station that a walk test has begun.

2. Violate all each detector (zone) in sequence. A squawk will occur at the keypad and the violation will be 

recorded in the Event Buffer.

3. Restore zones. Press 

 to end the Walk Test. The system will notify the Central Station that the walk 

test has been terminated.

Note:  If a zone is not violated within 15 minutes of activating the Walk Test, the system will automatically exit the 
Walk Test and resume normal operation. 

6

6

http://www.ealarm.com.my

Содержание PowerSeries LCD5500Z

Страница 1: ... After Away Arming 7 Disarming Turning Off Unsetting 8 Stay Arming Partially Turning On Part Setting 8 Re activate bypassed zones 8 Silent Exit Delay 8 Remote Arming and Disarming 8 Emergency Keys 8 When Alarm Sounds 9 Intrusion Burglar Alarm Continuous Siren 9 Fire Alarm Pulsed Siren 9 Time Date Programm ng 9 Bypassing Zones 9 Trouble Conditions 11 Trouble Menu Acknowledgement 11 Alarm Memory 11 ...

Страница 2: ...t Buffer from an LCD Keypad 16 PK5500 Global Status Screen 16 Sensor Reset 16 Testing Your System 17 Testing Your Keypad Sounder and Siren 17 Testing Your Entire System 17 Walk Test Mode 17 Allowing Computer Access To Your System 17 Guidelines for Locating Smoke Detectors 18 Household Fire Safety Audit 19 Fire Escape Planning 19 h t t p w w w e a l a r m c o m m y ...

Страница 3: ...ler may have installed o e of these LED keypads if you have 16 or fewer zones on your sys tem These keypads operate in the same way as the PC5532 keypad PC5508Z PC5516Z Status Lights Number Pad Function Buttons Liquid Crystal Display LCD Arrow Scroll Keys Emergency Keys LCD5501Z LCD5500Z h t t p w w w e a l a r m c o m m y ...

Страница 4: ... 8 0 9 Stay Away Chime Reset Bypass PK5508 PK5516 shown PK5500 PK5501 Status Lights Number Pad Emergency Keys Zone Lights PC1555RKZ LCD5511 Display System Lights Number Pad LED5511 h t t p w w w e a l a r m c o m m y ...

Страница 5: ...turn off when the chime function key is pressed again to disable Door Chime 12 AM PM This icon indicates tha th local clock is displaying 12 Hr time These icons will not be on if the system is pro grammed for 24 Hr time 13 ALARM This icon is used w th clock digits 1 and 2 to indicate zones in alarm on the system When a zone is in alarm the ALARM icon will turn on and 7 segment displays 1 and 2 wil...

Страница 6: ...29 03 12 21 30 04 13 22 31 05 14 23 3 06 15 24 3 Duress 07 16 25 34 Duress 08 17 26 09 18 27 The Entry Delay Time is _______ seconds The Exit Delay Time is _______ seconds For Service Central Station Information Account ___________________ Telephone __________________ Installer Information Company ___________________ Telephone __________________ If you suspect a false alarm signal has been sent to...

Страница 7: ... Sensor Protected Area Sensor Type 01 33 02 34 03 35 04 36 05 37 06 38 07 39 08 40 09 41 10 42 11 43 12 44 13 45 14 46 15 7 16 48 17 49 18 50 19 51 20 52 21 53 22 54 23 55 24 56 25 57 26 58 27 59 28 60 29 61 30 62 31 63 32 64 h t t p w w w e a l a r m c o m m y ...

Страница 8: ...tting alarms troubles and me gency information over telephone lines to a cen tral station If you inadvertently initiate an alarm immedi tely call the central station to prevent an unnecessary response NOTE The monitoring function must be enabled by the installer before it becomes functional SIA NOTE There is a communicator delay of 30 seconds in this control panel It can be removed or it can be in...

Страница 9: ...d hold the Away key for 2 seconds and r enter your Access Code or press to Quick Arm During the setting state exit delay active the A med and Ready indicators will turn on and the key pad will sound one beep per second You now have ____ seconds to leave the premises please check with your installer to have this time programmed To cance e arming sequence enter your access code Away Arming Turned On...

Страница 10: ...system will automatically bypass certain interior sensors i e motion sensors NOTE For SIA FAR listed panels the Stay Arming Exit D lay will be twice as long as the Away Arming Exit Delay Re activate bypassed zones To fully arm the system when it has been armed in S y mode Press at any keypad The interior zones ar ow armed NOTE When the interior zones have been re ac vated you will not be able to e...

Страница 11: ...g feature when you need ac ess to a protected area while the system is armed or when a zone is temporarily out of service but you need to arm the system Bypassed zones will not be able to sound an alarm Bypassing zones reduces the level of se urity If you are bypassing a zone because it is not working call a service technician immediately so that th problem can be resolved and your system returned...

Страница 12: ...1 Press then your access code if necessary 2 Press 3 To exit bypassing mode and return to the Ready tate press Bypass Groups A Bypass Group is a selection of zones pr g ammed into the system If you bypass a group of zones on a regular basis you can program them into the Bypass Group so that you do not have to bypass each zone individually every time One Bypass Group can be programmed on each parti...

Страница 13: ...r press Access Code Programming In addition to the Master Access Code you can program up to 32 additional User Access codes Press plus your Master Access Code The Program or System indicator will begin to flash and the Armed indicator will turn on Enter the 2 digit number to be programmed i e 06 for user access code 6 enter 40 for the Master Access Code When using the LCD5500 use the keys to find ...

Страница 14: ...e Duress Reporting Code whenever the code is entered to perform any func on on the system NOTE Duress codes are not valid when entering 5 6 or 8 sections NOTE No codes can be programmed as a duplicate of another code NOTE Duress codes cannot be programmed as a duplicate or as a Code 1 User Code Attributes 1 The default attributes of a new code will be the at ibutes of the code used to enter whethe...

Страница 15: ...ee Access 4 Partition Four Access 5 Partition Five Access 6 Partition Six Access 7 Partition Seven Access 8 Partition Eight Access Notes on Access Codes and Programming 1 There will still be 37 codes if option selected for 6 digit access codes 5 MASTER CODE 01 to 32 33 34 40 41 42 to program access codes 5 MASTER CODE 8 enters the Partition Assignment Mode 01 to 32 33 34 41 42 to edit access code ...

Страница 16: ...dby battery 5 Enable DLS Allow System Service If enabled the installer will be able to access Installer Programming by DLS In case of DLS access this provides a window where rings will be detected by the panel The DLS window will remain open for 6hrs during which time the installer will be able to enter DLS an unlimited number of times After the 6 hr window has expired Installer s Programming will...

Страница 17: ...ough 21 different buzzer levels A level of 00 disables the buzzer 1 Press Master Code 2 Use the keys to scroll to Buzzer Control 3 There are 21 different levels use the keys to scroll to the desired level PK5501 PK5508 PK5516 keypads 1 Press Master Code 2 Use the key to move through the 2 different buzzer levels 3 The level is automatically saved when you press to exit Label Programming PK5500 LCD...

Страница 18: ... press PK5500 Global Status Screen When the keypad is loaned to global mode pressing and holding the key you will see a Global Partition Sta tus screen This shows basic status for up to 8 partitions d pending on the configuration of your system The screen looks similar to the example shown below 1 3 4 5 6 7 8 A R N Each partition is identified by a number B w each number is the current status of t...

Страница 19: ...when each zone detector is activated Secure System Before Arming Secure System or Enter Code or Secure or Arm System Use the keys to view which zones are open The message will disappear when the zones are closed On an LCD5501Z keypad the display says pen when any zone detector is activated To see which zones are open press The keypad w l scroll the numbers of all open zones On a PC55XXZ keypad the...

Отзывы: