51
GB
Cleaning up of refrigerant
General Measures:
1. Gas/vapor heavier than air. May
accumulate in confined spaces,
particularly at or below ground level.
2. Eliminate every possible source of
ignition.
3. Use appropriate personal protection
equipment (PPE).
4. Evacuate unnecessary personnel, isolate,
and ventilate area.
5. Do not get in eyes, on skin, or on
clothing. Do not breathe vapors or gas.
6. Prevent entry to sewers and public
waters.
7. Stop the source of the release, if safe to
do so. Consider the use of water spray to
disperse vapors.
8. Isolate the area until gas has dispersed.
Ventilate and gas test area before
entering. Contact competent authorities
after a spill.
Troubleshooting
Symptom
Inspection
Solution
The appliance is not
operating.
Check the power connection
in securely.
Insert the power cord securely into
the wall outlet.
Check if the water level
indicator lights up?
Empty the drain pan by remove the
rubber plug.
Check the room
temperature.
The range of operating temperature
is 5-35 °C.
The appliance
works with reduced
capacity.
Check the air filter for dirt.
Clean the air filter as necessary.
Check if the air duct is
blocked.
To clear the obstacle.
Check if the room door or
window is open.
Keep the door and windows closed.
Check if the desired
operating mode is selected
and the temperature is
properly set.
Set the mode and temperature
at proper set-point according the
manual.
The exhaust hose is
detached.
Make sure the exhaust hose is
securely attached.
Water Leakage
Overflow while moving the
appliance.
Empty the water tank before
transport.
Check if the drain hose is
kinked or bends.
Straighten the hose to avoid a trap
existing.