11
Model
Power
(KW)
Phase&
Voltage
(V)
Current
Drawn (A)
Fuse &
Residual
Current
Device
(A)
Cable
Section
(mm)
UKDAX-
60ETP
60
3~400
3*90,9
3*100
5*25
UKDAX-
72ETP
72
3~400
3*109,1
3*125
5*35
UKDAX-
80ETP
80
3~400
121,2
3*150
5*35
UKDAX-
96ETP
96
3~400
145,5
3*160
5*50
Make sure that cables are connected to correct places.
. Loose cable connections can be caused to accidents.
Cable sections that are calculated according to device capacity and cable
length, residual current device and fuse amper values can be seen at the
following table.
Cable sections at this table are calculated for maximum 10m. Consult your
authorised service for more than 10m cable length.