II.
Input module initial register (0x1000)
The control module will, based on the user’s module configuration, automatically
assign each module an input module register based on the modules’ functions, types
(digital or analog), station number and data consumption.
The registers are assigned based on the priority below:
Digital
Analog
Station
number
The output initial register address for the (digital) input module with the lowest
station number: 0x1000.
Example: With 2 digital input modules (station number 1 and 4) and 2 analog input
modules (station number 2 and 3), the control module will assign the following input
module registers:
Digital input module (station No.1)
: 0x1000 (output initial register; takes up 1
WORD of data)
Digital input module (station No.4)
: 0x1001 (a range of registers assigned by the
control module, with the address of 0x1001 (1 higher than
the 0x1000 of the station No.1 register address; takes up 1
WORD of data)).
Analog input module (station No.2)
: 0x1002~ 0x1005 (a range of registers
assigned by the control module, with the address of 0x1002
(1 higher than the 0x1001 of the station No.4 register
address; takes up 4 WORD of data)).
Analog input module (station No.3)
: 0x1006~0x1009 (the control module, based
on the register assigned to station No.2 and its data
consumption, assigns the address of 0x1006 (1 higher than
the 0x1005 of the station No.2 register address)).
Содержание iO-GRID M
Страница 1: ...iO GRID M Control Module User Manual 2211TW V3 0 0 ...
Страница 7: ...7 3 Control module Information 3 1 Control Module Dimensions Unit mm ...
Страница 19: ...19 IV Click on the Setting Module icon V Enter the Setting Module page for M series ...
Страница 20: ...20 VI Select the mode type based on the connected module VII Click on Connect ...
Страница 24: ...24 XIII Fieldbus communication settings the format and baud rate must be the same as the I O module ...