25
7.
Control Module Register Configuration
I.
Control Module Register Assignment
The control module will, based on the user’s module configuration, automatically
assign each module a register address based on the modules’ functions, types (digital
or analog), station number and data consumption.
The registers are assigned based on the priority below: Digital
Analog
Station
number
Control module Register address assignment
The address for input initial registers starts from 0x1000;
the address for output initial registers starts from 0x2000;
A single piece of 16-channel digital module will take up 1 WORD
/
2 BYTE while
a single piece of 4-channel analog module will take up 4 WORD
/
8 BYTE of data.