background image

LOAD CHARACTERISTICS

WIRING DIAGRAM

WORKING DIAGRAM

HOW TO ORDER:

DAT 1112 -  1

The  transmitter must be powered with a voltage ranging from 12 to 32 V,  applied between the -V and  +V terminals.The
permissible Rload resistance, equivalent to that of the instruments applied in series to the voltage generator, must be
determined as a function of the power supply voltage value and according to the load characteristic so that its value is covered
by the working area. DAT 1112 is available in 6 different versions, covering all common sensors types. For most used sensors
a single unit cover 2 sensors, allowing substantial reduction of stocks.For programming the device, see the technical sheet
" DAT 1112 Programming Instruction ". Once the device is programmed, the calibration is carried out by adjusting the zero
and the span potentiometer as follows: apply a signal corresponding to desired minimum input signal and than adjust  the
zero potentiometer to get Iout = 4,00 mA. Apply a signal corresponding to desired maximum input signal and than adjust  the
span potentiometer to get Iout = 20,00 mA. Repeat these operations until the needed accuracy is obtained.

DIMENSIONS

(measures in mm.)

Version

VERSION TABLE

Version

Sensor

Programmable Span

1

2

3

4

5

6

K & J

R & S

E

N

B

T

100 - 1400°C / 200 - 2500°F (K)
100 - 950°C / 200 - 1800°F (J)

650 - 1760°C / 1200 - 3200°F (R)
700 - 1760°C / 1290 - 3200°F (S)

100 - 350°C / 200 - 600°F 

900 - 1820°C / 1600 - 3250°F 

150 - 1350°C / 250 - 2400°F 

50 - 1050°C / 100 - 1900°F 

MAIN

AMP.

LINEARIZER

TWO WIRE

TRANSMITTER

+V

-V

1

2

- TC

+ TC

COLD

JUNCT.

COMP.

INTERNAL
REFERENCE 
GENERATOR

5

4

TC

RLoad

+

-V

+V

1

2

3

+

7

43

17

33

ZERO

SPAN

ON

1

8

OPERATING INSTRUCTIONS

Содержание DAT1112

Страница 1: ...ns conditioning cold junction compensation and current transmission thanks to the employement of high precision and high quality components and to the use of the SMD technology The device conform to the 89 336 EEC directives on electromagnetic compatibility is housed in a rugged self extinguishing plastic case suitable for direct mounting on the connection head TECHNICAL SPECIFICATIONS Typical 25 ...

Страница 2: ...he device is programmed the calibration is carried out by adjusting the zero and the span potentiometer as follows apply a signal corresponding to desired minimum input signal and than adjust the zero potentiometer to get Iout 4 00 mA Apply a signal corresponding to desired maximum input signal and than adjust the span potentiometer to get Iout 20 00 mA Repeat these operations until the needed acc...

Страница 3: ...ERO PROGRAMMING SPAN PROGRAMMING Range SW4 SW2 It is not necessary because the transmitter is able to operate either with the thermocouple R or the thermocouple S It is not necessary Zero could be adjusted from 50 C up to 50 C by the appositely dedicated ZERO adjusting potentiometer It is not necessary Zero could be adjusted from 50 C up to 50 C by the appositely dedicated ZERO adjusting potentiom...

Страница 4: ...he dei propri prodotti senza alcun preavviso Datexel reserves its right to modify the characteristics of its products totally or in part without warning at any time Version 5 thermocouple N SPAN PROGRAMMING Sensor Range SW4 SW2 150 C to 200 C ON OFF 200 C to 480 C ON ON 480 C to 580 C OFF OFF N 580 C to 1300 C OFF ON ZERO PROGRAMMING Sensor Range SW3 SW1 N 50 C to 15 C 15 C to 50 C OFF ON OFF OFF ...

Отзывы: