PQRM5100 11 Ux Ix xx xx (PS)
20200205-V1
43
“Between limits”
The output changes into active state when measured value
is between of range upper and lower limit as the monitored
value. The output changes into inactive state when
measured value is out of range as the monitored value. The
hysteresis is like the high and low limit functions can use it.
“Out of limits”
The output changes into active state when measured value
is out upper and lower limit as the monitored value. The
output changes into inactive state when measured value is
between of range upper and lower limit as the monitored
value. The hysteresis is like the high and low limit functions
can use it.
7. Type-in the high limit value into the “Upper limit” field.
8. Type-in the low limit value into the “Lower limit” field.
9. Type-in the hysteresis value into the “Hysteresis” field.
The whole hysteresis value is the double of the typed-in
value.
10. Click on the “Save” button.