DT9500
20220103-V2
19
Wiring plan, connecting
the limit outputs
(see also “Application
example”)
Be careful the polarity of the cables.
Select connection cable
Select connection cable
for Ex applications
Take note the suitability of the connecting cable.
We recommend the use of screened twisted pair cable.
The wire cross-section should be 0.25-1.5 mm
2
.
Take note of the corresponding installation regulations for
Ex applications. In particular, make sure that no potential
equalisation currents flow over the cable screen. In case of
grounding on both sides (for suppress the influence of high
frequency interference signals) this can be achived by use
of a capacitor (e.g. ceramic capacitor 1 nF, 1500 V) or
separate potential equalisation. The low frequency
potential equalisation currents are thus supressed, but the
protective effect against high frequency interference
signals remains.
Inserting the cable into
the instrument
1. Prepare the cable for the connection.
Remove approx. 30 mm of cable mantle, strip approx.
8 mm insulation.
2. Remove the instrument front cover (see chapter
4.3.).
3. Loosen compression nut of the cable entry.
4. Insert the cable into the instrument through the cable
entry.
Содержание DT9500
Страница 1: ...DT9500 Intrinsically Safe Temperature Meter Transmitter Operating Instructions ...
Страница 67: ...DT9500 20220103 V2 67 10 2 Application example ...
Страница 87: ...DT9500 20220103 V2 87 10 9 ATEX Certification ...
Страница 88: ...DT9500 88 20220103 V2 ...
Страница 89: ...DT9500 20220103 V2 89 ...
Страница 90: ...DT9500 90 20220103 V2 ...
Страница 91: ...DT9500 20220103 V2 91 ...
Страница 92: ...DT9500 92 20220103 V2 ...
Страница 93: ...DT9500 20220103 V2 93 ...
Страница 94: ...DT9500 94 20220103 V2 ...
Страница 95: ...DT9500 20220103 V2 95 ...
Страница 96: ...DT9500 96 20220103 V2 ...
Страница 97: ...DT9500 20220103 V2 97 ...
Страница 98: ...DT9500 98 20220103 V2 ...
Страница 99: ...DT9500 20220103 V2 99 ...
Страница 100: ......