background image

iBoot Ver 1.5  Page 15  

Upon Clicking Reboot, a page 
indicates the new URL for the 
device.  Use this new URL to 
access iBoot. 

 

 
 
 
 
 
 
 
 
 
 

Ping Address

: Enter the IP address of the device to be pinged. 

 

Ping Frequency

: Enter 1 to 999 seconds.  The ping will go out to the selected 

device this often. 
 

Fail Counter:

  Enter 1-99 times the ping needs to fail before the selected action 

is taken. 
 

Action

: select from  

♦ 

None   (Auto Ping not used) 

♦ 

Power On – Latch 

♦ 

Power On – Follow 

♦ 

Power Off – Latch 

♦ 

Power Off – Follow 

♦ 

Power Cycle 

♦ 

Power Cycle Once 

 
Power On – Latch:  Upon loss of ping response, iBoot will power on and remain 
so until changed via the web, ibootctl.exe or direct messaging. 

Power On – Follow: Upon loss of ping response, iBoot will power on.  When the 
ping response returns, iBoot will power off. 

Power Off – Latch:  Upon loss of ping response, iBoot will power off and remain 
so until changed via the web, ibootctl.exe or direct messaging. 

Power Off – Follow: Upon loss of ping response, iBoot will power off.  When the 
ping response returns, iBoot will power on. 

Power Cycle:  Upon loss of ping response, iBoot will cycle the power.  iBoot will 
wait the Ping Frequency; if the response does not return, the power will be 
recycled again.  This will continue until the ping response returns or Auto Ping is 
turned off.  Make sure your Auto Ping frequency is longer than the time required 
to reboot your device. 

Power Cycle Once:  Upon loss of ping response, iBoot will cycle power one time. 
It will not cycle again automatically until the ping response returns and is lost 
again. 

 

Home:

 Return to the main screen 

 

Remember to click Apply for each section you are changing.

 

Содержание iBoot

Страница 1: ...n 9 Setting IP Address Using DHCP Using Web Browser Access Using ibootrst exe Using ARP Ping Web Browser Operation 12 Password Protection Control Status Page Setup Page Passwords Page Forgotten Passwo...

Страница 2: ...ong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this product...

Страница 3: ...ps 10 Amps at 230VAC Uses for iBoot Remote reboot of any device routers servers kiosks etc The device to be rebooted need not be network attached Secure sensitive devices by keeping them powered off w...

Страница 4: ...reboot it automatically when it no longer responds Use Auto Ping Remotely Put iBoot at a central facility to monitor a remote system and power up an alert when the remote device no longer responds Up...

Страница 5: ...disconnect the iBoot from the AC power source before making any control connections 10 100 Ethernet Power Input IEC 320 Male Line Cord Incuded for North America Power Input Selector 115 230 VAC Power...

Страница 6: ...ovided Use the Uplink jack to connect to an Ethernet hub and the Downlink jack to connect to an additional piece of networking equipment An LED next to each indicates when the connection to the networ...

Страница 7: ...Connect to Power Source Use Included Cord for North America For other locations use locally approved power cord 1 2 3 Connect Powered Device Use either IEC to NEMA Extension Cord supplied OR IEC to IE...

Страница 8: ...device to be power controlled The iBoot can be connected to a power strip to allow simultaneous control of multiple devices Make sure that the combined load of all controlled devices does not exceed 1...

Страница 9: ...et Mask and Gateway to the iBoot If you power up iBoot without a fixed static IP address the DHCP server will be able to assign an IP address This is the factory default setting for iBoot Once an IP a...

Страница 10: ...r ibootrst exe For iboot exe http www dataprobe com files power iboot exe To use ibootrst exe the computer running the program must be on the same subnet and network segment as the iBoot is to be prog...

Страница 11: ...d the MAC address is the MAC Address of the iBoot The MAC Address of the iBoot is located on bottom of the unit Example arp s 63 211 86 165 00 50 c2 05 01 c1 enter new IP addr MAC addr 3 Ping the iBoo...

Страница 12: ...rd if it has been changed A Username is not required When the proper password is received the Control and Status Page is displayed Control and Status Page Once the password is entered the following pa...

Страница 13: ...dow without first clicking Logout there will be a two minute delay before you can re access iBoot iBoot uses an inactivity timer for security When there is no activity for 2 minutes the user is logged...

Страница 14: ...he top of the page The new IP address will not take effect until the unit is rebooted Subnet Mask Change if required Consult your network manager for more details This will be automatically set if usi...

Страница 15: ...on When the ping response returns iBoot will power off Power Off Latch Upon loss of ping response iBoot will power off and remain so until changed via the web ibootctl exe or direct messaging Power Of...

Страница 16: ...for each password being changed OOPS I forgot my Password Well we told you to remember it but we understand You can reset iBoot to its factory default conditions Dataprobe provides a iBoot Reset Progr...

Страница 17: ...r ibootctl exe or http www dataprobe com files power iboot exe for ibootctl exe and ibootrst exe the reset program Direct TCP Telnet Control For application developers iBoot also supports control via...

Страница 18: ...Input 3 Prong Male IEC 320 input connector Input Cord Spec 16AWGX3C 10A 250 UL CSA VDE Rated 1 25mm 2 X3C Voltage Range Selectable 115 or 230 VAC Switched Receptacle 3 Prong Female IEC Capacity 12 Amp...

Страница 19: ...al Service at 201 967 8788 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipment T...

Страница 20: ...functions be enabled User selectable security call processing and power control features are examples of such capabilities Visit www dataprobe com power ppal html Remote Power Control Console Port Ac...

Отзывы: