Page 15 

 

5.5. 

Automation 

 
Automation  settings  page  shows  the  current  status  of  the  AutoPing  and  Traffic  Monitors  that  are  set.    It 
also allows Automatic Configuration of these settings. 
 
The  Traffic  Monitor  shows  the  current  throughput.    This  will  update  each  time  the  Refresh  button  is 
pressed. 
 
To have the iBoot-PoE-P re-examine the network and auto-set the automation capabilities, press the Auto 
Config button. 
 
 

AutoPing  

Two separate Auto Ping addresses can be 
set with And/Or logic.   
 
 
Address:  Enter  the  IP  address  of  the 
device, or domain name to be pinged.  To 
enter  the  second  address  and  settings, 
select AND or OR for the A/B Logic.  
 
Ping  Frequency:  Enter  1  to  999  seconds.  
The ping will go out to the selected device 
this often. 
 
Fail  Count:    Enter  1-999  times  the  ping 
needs  to  fail  consecutively  before  the 
selected  action  is  taken.    When  the  fail 
count  has  been  reached,  the  AutoPing 
action will be triggered. 
 
Mode:    Select  from  Single,  AND,  OR.  
With AND, both AutoPings need to exceed 
their fail count to trigger the Action.  With OR, the Action will be triggered if either AutoPing fails. 
 

 

Action:  Select from 

 

None 

AutoPing is paused.  No Ping tests will be performed. 

Power On 

– Latch 

Upon triggering, iBoot-PoE-P will power on and remain so until changed via 
the web, telnet, DxP, etc. 

Power On 

– Follow 

Upon  triggering,  iBoot-PoE-P  will  power  on.    When  the  ping  response 
returns, iBoot-PoE-P will power off. 

Power Off 

– Latch 

Upon triggering, iBoot-PoE-P will power off and remain so until changed via 
the web, telnet, DxP, etc. 

Power Off 

– Follow 

Upon  triggering,  iBoot-PoE-P  will  power  off.    When  the  ping  response 
returns, iBoot-PoE-P will power on. 

Cycle  
Cycle Times 
 

Upon triggering, iBoot-PoE-P will cycle the power.  If Power Cycle does not 
result in the ping response the iBoot-PoE-P can cycle again.  The number of 
times the iBoot-PoE-P will cycle is set by the 

Cycle

 

Times

 setting.  To have 

the  iBoot  cycle  power  3  times  to  get  the  system  to  respond  again,  set  the 
Cycle Times to 3.   

 
Restart:  This  setting  delays  the  restart  of  the  AutoPing  tests  after  the  Action  is  completed.    This  setting 
allows time for the boot sequence of the failed device to complete.     

Содержание iBoot PoE-P

Страница 1: ...ty 31 Congratulations on purchasing the best network controlled power switch available The iBoot PoE P provides you the ability to reboot crashed devices automatically or with the click of a mouse Be...

Страница 2: ...Reboot iBoot PoE P has a web server built in as well as the ability to be managed through the iBoot Cloud Service A simple Web browser interface makes it easy to control power from anywhere in the wo...

Страница 3: ...it is also possible to turn ON or OFF the PD when the trigger conditions are met See Section 5 5 On AutoPing Setup Traffic Monitor Traffic Monitor measures the bandwidth utilization and reboots the PD...

Страница 4: ...mputer control URL Control You can send a single URL to the iBoot PoE P containing all the information necessary to query or change the power status This makes it easy to create a single button on you...

Страница 5: ...ctor Auto Configuration can also be initiated via the web page setup See Section 5 5 2 2 Hardware Connections iBoot PoE P supports 10 100 1000 Ethernet using the cable supplied or other suitable unshi...

Страница 6: ...Voltage on all pins 1 DC DC 2 DC DC 3 DC DC 4 DC DC 5 DC DC 6 DC DC 7 DC DC 8 DC DC Power Output on the PoE OUT connector will be identical to whatever mode is used on the NET IN connector 2 4 Mountin...

Страница 7: ...he iBoot PoE P Obtain and use the DMU 1 Download the latest version of the DMU at dataprobe com support iboot poe Run DMUSetup exe 2 Run the DMU Note The IP address can only be set within the first tw...

Страница 8: ...utton Get all the details on the DMU at http dataprobe com support dmu 3 3 Other ways to set the IP Address 1 Web Browser via the Set up Page See Section 5 2 Command Line Interface See Section 9 3 4 A...

Страница 9: ...setup or Command Line Interface See Section 5 5 for an explanation of these settings AutoPing Setting Address IP Address of Powered Device Frequency 10 Seconds Fail Count 3 Mode Single Action Cycle Re...

Страница 10: ...tes Setting to zero disables the timeout feature When there is no activity for the set time in minutes the user is automatically logged out and the username and password will need to be entered again...

Страница 11: ...ded If the iBoot PoE P is connected to a time server see Section 5 4 The Home page will also show the five most recent history events including the Outlet Action User and Time Date of each event The i...

Страница 12: ...not significant The user and password are not required when Auto Login feature is enabled see Section 5 7 for security options Examples http 192 168 1 254 s 1 u user p user Turn the outlet on for the...

Страница 13: ...emote firmware upgrades of the iBoot PoE P When this box is unchecked firmware upgrades will not be allowed Auto Logout This setting sets the automatic logout for inactivity on both the web and telnet...

Страница 14: ...able Cloud Services This setting enables the iBoot PoE P for iBoot Cloud Services iBCS iBCS allows the iBoot PoE P to be monitored and controlled from a web portal from any browser It allows multiple...

Страница 15: ...oth AutoPings need to exceed their fail count to trigger the Action With OR the Action will be triggered if either AutoPing fails Action Select from None AutoPing is paused No Ping tests will be perfo...

Страница 16: ...fic Subsequent reboots will occur when the time equals the Restart Time plus the Fail Time Number of Cycles Set the number of reboots to attempt for a single failure event Minimum Traffic Sets the min...

Страница 17: ...de supports both User and Admin users Each user has a settable password Auto Login This mode does not require a username of password for the User level operation No login challenge will be required fo...

Страница 18: ...will not allow programming for On Follow Off Latch or Off Follow If a Schedule Settings event has action for Off it will be reprogrammed for On Schedule Settings will not allow programming for action...

Страница 19: ...ice name when on the local network By default the name is iBoot PoE P xxxx where the xxxx is the last 4 segments of the MAC address for your iBoot PoE P When you reprogram the name of the device a reb...

Страница 20: ...Boot firmware may be made available and necessary to keep current with the cloud development The full Terms of Service of the iBoot Cloud Service is available here While the Cloud Service is in Beta s...

Страница 21: ...click on Add Device and enter the activation code in the field provided Congratulations You are now on the cloud d iBCS Main Page The iBCS main web page provides the ability to control your iBoot PoE...

Страница 22: ...to Password Enter the admin or user password and press Enter The prompt will change to iBoot This indicates successful login Enter commands as needed When done enter the logout command Note The telnet...

Страница 23: ...etwork This command will return all the network settings as shown below Mode DHCP IP Address 192 168 1 254 Subnet 255 255 255 0 Gateway 192 168 1 1 DNS 8 8 8 8 HTTP Port 80 Linkback URL Telnet Port 23...

Страница 24: ...decimal or name This command is used to set the address of AutoPing 1 or AutoPing 2 Use IP Address or domain name set autoping 1 2 frequency 1 999 This command is used to set the frequency how often t...

Страница 25: ...the stop disable time 00 00 get traffic monitor Traffic Monitor Enabled or Disabled Fail Time in seconds Restar Time in seconds Number of Cycles Minimum Bandwidth as programmed Maximum Test enabled d...

Страница 26: ...d to set the Address of a network time server ip or FQDN time nist gov get time Displays the current time and time server settings Current Time 07 30 2015 10 41 05 Timezone 5 DST Enabled Starts the 2n...

Страница 27: ...at the user is presented with Password This prompts the user to enter his password iBoot This is the prompt that will be displayed after the user has successfully logged in iBoot Reboot Required This...

Страница 28: ...es for the upgrade before making changes to you iBoot PoE P 1 Insure that the Upgrade Enable checkbox is checked in the Network Setup web page of the iBoot PoE P 2 Run the Device Management Utility av...

Страница 29: ...e output status 5 Seconds push Reset to Factory Defaults Hold the button in until the Outlet LED is blinking then release Hold in while and Power up the iBoot Recovery Mode Allows upload of new firmwa...

Страница 30: ...ce FCC Part 15 Class B CE Emission EN 55032 2012 AC 2013 CISPR 32 2012 Class B AS NZS CISPR 32 2013 EN 61000 3 2 2014 and EN 61000 3 3 2013 Immunity EN 55024 2010 A1 2015 IEC 61000 4 2 2008 IEC 61000...

Страница 31: ...r this Warranty is obtained by contacting your Authorized Dataprobe Reseller THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EX...

Отзывы: