Continue with the following steps to switch from condition 2 to condition 1:
1. Keep the receiver in a steady position and regulate the emitter until the yellow LED (
SYNC) is OFF. This condition
shows the effective alignment of the first synchronization beam.
2. Rotate the emitter, pivoting on the lower optics axis, until the yellow LED (
LAST) is OFF. Under these conditions,
if no other beam is intercepted Alignment LED (
) should turn GREEN.
3. Delimit the area in which the LED
is steady GREEN through some micro adjustments - for the first and then for
the second unit - then place both units in the centre of this area.
Fix the two units firmly using brackets.
Verify that the green LED on the RX unit is ON (
) and beams are not interrupted, then verify that the red
LED turns ON if even one single beam is interrupted (condition where an object has been detected).
This verification shall be made with the special cylindrical “Test Piece” having a size suitable to the resolution of the
device used.
A daily test is recommended.
DEVICE DESCRIPTION FILE
Importing device in B&R automation studio
In order to make the light curtain available in Automation Studio it’s necessary to import the description files in Automation
Studio.
1. Select Tools -> Import Fieldbus Device
Step 1 - Importing the device
Ensure that the green LED
is steady ON.
Passing the Test Piece along the whole sensitive area and at any distance from the two
units, the red LED (
) shall be always ON and never change status.