Visualization Status
Description
Action
INTERLOCK
Free beams, OSSDs OFF
User can take device in normal
operation activating restart line.
INTERLOCK
Interrupted beams, OSSDs
OFF
User must free beams path before
activating restart line.
NORMAL OPERATION OSSDs ON
SAFE
OSSDs OFF, No code
SAFE
OSSDs OFF, Code 1
SAFE
OSSDs OFF, Code 2
NORMAL
OPERATION, SAFE,
INTERLOCK
EDM function active
EDM function not active
SAFE,
INTERLOCK
Override function ready to
be activated
User can activate Override function
activating the correct sequence on
Override lines.
FAILURE LOCKOUT
(recoverable)
Failure on one or both
OSSDs, OSSDs OFF
User must activate RESET line. If
ESPE does not reset user must
contact Datalogic.
FAILURE LOCKOUT
(not recoverable)
Microcontroller failure,
OSSDs OFF
User must turn OFF/ON ESPE. If
the problem persists user must
contact Datalogic.
FAILURE LOCKOUT
(recoverable)
Optical failure, OSSDs OFF
User must activate RESET line. If
ESPE does not reset user must
contact Datalogic.
FAILURE LOCKOUT
(recoverable)
EDM failure, OSSDs OFF
User must check EDM ENABLE line
or dip-switches, EDM line, external
switching device and activate
RESET line. If ESPE does not reset
user must contact Datalogic
Automation Technical Support.
FAILURE LOCKOUT
(not recoverable)
Override connection failure,
OSSDs OFF
User must check Override lines
connection and turn OFF/ON ESPE.
If the problem persists user must
contact Datalogic Automation
Technical Support.
SAFE
Override sequence failure,
OSSDs OFF
User must check Override lines
activation sequence timings and
repeat Override sequence. If the
problem persists user must contact
Datalogic.
FAILURE LOCKOUT
(not recoverable)
Dip switch failure, OSSDs
OFF
User must check dip-switch
configuration (see par.” DIP
SWITCHES CONFIGURATION”)
and turn OFF/ON ESPE. If the
problem persists user must contact
Datalogic Automation Technical
Support.
FAILURE LOCKOUT
(recoverable)
Internal and external lamp
failure, OSSDs OFF
User must check LAMP INPUT line
and activate RESET line. If ESPE
does not reset user must contact
Datalogic.
ESPE OFF
Power supply failure,
OSSDs OFF
User must check power supply
connection. If the problem persists
user must contact Datalogic.