SET Button: 0.04 seconds  "Click"  0.8 seconds 
Remote Input: 0.04 seconds  T  0.8 seconds 
 

17
18

 

Calibration SET

 

 

Sets a threshold exactly at the presented condition 

 

Threshold can be adjusted using "+" and "-" Navigation key (Manual Adjust) 

 

A single sensing condition is presented, and the sensor positions a threshold exactly at the presented condition. When a condition lighter 
than the threshold is sensed, the output either turns ON or OFF, depending on the LO/DO switch setting (see 

LO/DO Switch 

in 

Top Panel 

Interface

). 

Threshold position 

adjusted by 

Manual Adjust

 

 

 

 

 

Sensor positions 

threshold exactly at

 

the presented condition

 

 

 

 

Output OFF

 

 

Output ON

 

Darkest 

(no signal)

 

Condition 

Presented

 

Most Light 

(saturated 

signal)

 

Figure 8. Calibration SET (Light Operate shown)

 

Calibration SET and Manual Adjust

 

Moves switching threshold value up or down to make adjustments 

 

Slide Mode switch to ADJ to enter Adjust mode 

 

Press "+" to increase; press "-" to decrease 

-  GREEN display shows the switching threshold value 
-  2 seconds after adjustment, the GREEN display will flash 3 times to confirm 

 

Slide Mode switch to RUN to complete operation 

 

 

 

 

Follow these steps to perform a Calibration SET: 

 

 

 

1.

 Enter 

Adjust 

Mode 

 

Method

 

Action

 

Result

 

 

SET Button 

17

 

 

 

Set Mode switch to ADJ 

 
 

Display: Red - Signal Level;  
            Green - Threshold 

Remote Input 

18

 

No action required; sensor is ready for 
Calibration SET method 

 

Remember

: Auto Thresholding is automatically disabled in Calibration SET 

Note

: TEACH Selection must be programmed to 

CAL SEt

 (see 

Program Mode

Содержание S70

Страница 1: ...or malfunction can cause either an energized or de energized sensor output condition Outputs Connector1 S70 2 E1 N Single NPN 2 m cable 4 wire S70 2 E1 P Single PNP S70 5 E1 N Single NPN Integral M8 Pico QD connector 4 pin S70 5 E1 P Single PNP S70 5 E1 PZ Dual outputs 1 push pull IO Link and 1 PNP complementary outputs S70 5 E2 N Single NPN Integral M8 Pico QD connector 4 pin S70 5 E2 P Single PN...

Страница 2: ... Move the fiber clamp backward to lock the fiber s 5 Close the dust cover Fiber Adapters NOTE If a thin fiber with less than 2 2 mm outer diameter is used install the fiber adapter provided with the fiber assembly to ensure a reliable fit in the fiber holder Datalogic includes the adapters with all fiber assemblies Fiber Outer Diameter mm Adapter Color Ø 1 0 Black Ø 1 3 Red Ø 2 2 No adapter needed...

Страница 3: ...the sensing condition is outside the window SET Navigation key The SET Navigation key is a 3 way button The positions are engaged by rocking the button left right The SET position is engaged by clicking down the button while the rocker is in the middle position All three button positions are used during PRG mode to navigate the display driven programming menu During ADJ mode SET is used to perform...

Страница 4: ...e value see Technical Data pag 17 Auto thr Click SET to enter choice list DISPLAY LOOP oFF On OFF dLY Click SET to enter choice 0 ms or to set value 9999 ms OFF 1Sho Click SET to enter choice list 0 ms or to set value 9999 ms SET Navigation key To scroll through menu lists Press or To enter a choice list or to select and save Click SET To exit a choice list without saving Press and hold SET for 2 ...

Страница 5: ...al Position adjusted by Manual Adjust Most Light saturated signal Figure 2 Two Point TEACH Light Operate shown The Output ON and OFF conditions can be reversed by using the LO DO Light Operate Dark Operate switch see LO DO Switch in Top Panel Interface Two Point TEACH and Manual Adjust Moves switching threshold value up or down to make adjustments Slide Mode switch to ADJ to enter Adjust mode Pres...

Страница 6: ...ngle pulse the remote input 4 Return to Run mode Method Action Result SET Button Move the Mode switch to RUN Display Red Signal Level Green Threshold Remote Input No action is required sensor returns to RUN mode automatically Dynamic TEACH Teaches on the fly Establishes a single switching threshold Threshold can be adjusted using and Navigation key Manual Adjust Dynamic TEACH is best used when a m...

Страница 7: ... 1 Enter Adjust Mode Method Action Result SET Button 5 Set Mode switch to ADJ Display Red Signal Level Green Threshold Remote Input 6 No action required sensor is ready for Dynamic TEACH method 2 Enter Dynamic TEACH Method Action Result SET Button Click the SET Navigation key Display Flashes dYn tch then holds on 1234 dYn Remote Input T Single pulse remote input 3 Present ON and OFF Conditions Met...

Страница 8: ...ange state Sensing window center can be adjusted using and Navigation key Manual Adjust Recommended for applications where a product may not always appear in the same place or when other signals may appear See Program Mode in the user s manual for programming the Offset Percent setting to increase decrease the window size A single sensing condition is presented and the sensor positions window thre...

Страница 9: ... Action Result SET Button Present sensing condition Click the SET Navigation key Threshold Condition Accepted Displays read wInd SEt then alternate PASS with Offset10 Sensor returns to Adjust mode Threshold Condition Not Accepted Displays read wInd SEt then alternate FAIL with minimum Offset10 for sensing condition Sensor returns to Adjust mode Remote Input Present sensing condition T Single pulse...

Страница 10: ...nel Interface Threshold position adjusted by Manual Adjust Sensor positions threshold a programmable offset below the presentedcondition Output OFF Output ON Darkest no signal Condition Presented Most Light saturated signal Figure 6 Light SET Light Operate shown Light SET and Manual Adjust Moves switching threshold value up or down to make adjustments Slide Mode switch to ADJ to enter Adjust mode ...

Страница 11: ...ented condition Any condition lighter than the threshold condition causes the output to change state Threshold can be adjusted using and Navigation key Manual Adjust Recommended for applications where only one condition is known for example a stable dark background with varying lighter targets See Program Mode for programming the Offset Percent setting A single sensing condition is presented and t...

Страница 12: ... Signal Level Green Threshold Remote Input 15 No action required sensor is ready for Dark SET method 2 SET Sensing Condition Method Action Result SET Button Present sensing condition Click the SET Navigation key Threshold Condition Accepted Displays read dr SEt then alternate PASS with Offset16 Sensor returns to Adjust mode Threshold Condition Not Accepted Displays read dr SEt then alternate FAIL ...

Страница 13: ... no signal Condition Presented Most Light saturated signal Figure 8 Calibration SET Light Operate shown Calibration SET and Manual Adjust Moves switching threshold value up or down to make adjustments Slide Mode switch to ADJ to enter Adjust mode Press to increase press to decrease GREEN display shows the switching threshold value 2 seconds after adjustment the GREEN display will flash 3 times to ...

Страница 14: ...r returns to Adjust mode Threshold Condition Unacceptable Displays read cAL SEt then flashes FAIL Sensor returns to Adjust mode Remote Input Present sensing condition T Single pulse the remote input 1 Return to RUN Mode Method Action Result SET Button Move Mode switch to RUN Display Red Signal Level Green Threshold Remote Input No action required sensor returns to RUN mode automatically ...

Страница 15: ...he taught conditions sufficiently exceeds the required minimum minor sensing variables will not affect sensing reliability 600 PASS The difference of the taught conditions greatly exceeds the required minimum very stable operation Percent Offset after SET The Window Dark and Light SET methods will flash a offset on the displays after a PASS or FAIL SET Result Offset Meaning PASS with Offset Displa...

Страница 16: ... voltage NPN 1 5 V PNP IO Link 2 V IO Link 50 A at 30 VDC OutputProtection Protected against output short circuit continuous overload transient over voltages and false pulse on power up Output Response Time High Speed 200 μs Standard 500 μs Long Range 2 ms Extra Long Range 5 ms Super High Speed 10 μs High Speed 15 μs Fast 50 μs Standard 250 μs Medium Range 500 μs Long Range 1000 μs Repeatability H...

Страница 17: ...imensions in mm Datalogic S r l Via S Vitalino 13 40012 Calderara di Reno Italy Tel 39 051 3147011 Fax 39 051 3147205 www datalogic com Datalogic reserves the right to make modifications and improvements without prior notification 821002592 Rev C 182859C ...

Отзывы: