PWR-2400 INSTALLATION MANUAL 

 

 

1.2.2  Overload Protection 

 
In  the  event  of  sustained  output  current  overloading,  overload  protection  is  provided  where 
overload power is supplied as explained in the examples below: 
 
 
Example 1: Up to 120% power overload 
 
The  overload  is  supplied  for  approximately  12  seconds  and  then  is  reduced  (Voltage  and 
Current)  to  about  104%  power  continuously.  In  this  case  output  voltage  is  reduced  but 
remains above 20 Vdc. 
 

 

Figure 4 

– Overload Protection up to 120% 

 
 

 

Содержание PWR-2400

Страница 1: ......

Страница 2: ...ed in any form or by any means or for any purpose without the express written permission of Datalogic S p A and or its affiliates Datalogic and the Datalogic logo are registered trademarks of Datalogi...

Страница 3: ...tion 2 2 PRE INSTALLATION CHECKLIST 4 System Wiring DC Output 4 System Wiring AC Input 4 System Wiring Test 4 3 MECHANICAL INSTALLATION 5 3 1 Cabinet Mounting 5 3 2 Cable Insertion 6 4 ELECTRICAL CONN...

Страница 4: ...his symbol alerts the user they are about to perform an action involving either a dangerous level of voltage or to warn against an action that could result in damage to devices or electrical shock It...

Страница 5: ...ogic products are mainly designed for integration purposes into more complex systems For this reason it is under the responsibility of the system integrator to do a new risk assessment regarding the f...

Страница 6: ...Filtered Air Intake Filtered Cooling Fan Out AC Line Input Compression Connector DC Output Compression Connectors AC Line Input Terminal Block 7 8 9 10 Thermal magnetic circuit breakers 24 Vdc Termina...

Страница 7: ...ides protection through a Miniature circuit breaker MCB 4 A 1p C Char For each monophase switching power supply two output power supply status monitoring signals DC OK are provided to connect to an op...

Страница 8: ...vided where overload power is supplied as explained in the examples below Example 1 Up to 120 power overload The overload is supplied for approximately 12 seconds and then is reduced Voltage and Curre...

Страница 9: ...This procedure is repeated until the excessive current overload is resolved Figure 5 Overload Protection at 125 Example 3 150 power overload The overload is supplied for approximately 4 seconds and t...

Страница 10: ...ckage See par 3 1 SYSTEM WIRING DC OUTPUT 3 Connect your devices to the PWR according to the information in par 4 2 SYSTEM WIRING AC INPUT 4 To comply with EN 60950 1 2007 par 1 7 2 2 par 2 7 1 par 2...

Страница 11: ...Mount the bracket to the cabinet 2 Mount the cabinet to the frame Figure 7 Mounting Brackets IMPORTANT The cabinet must be installed vertically in such a way that the key lock is no higher than 1 90 m...

Страница 12: ...e 9 Prepare each cable by stripping the wires and inserting the compression connector nut Pass the cable through the compression connector and make sure there is enough length to easily reach the corr...

Страница 13: ...ONNECTIONS 4 1 DC VOLTAGE TERMINAL BLOCK Figure 10 PWR 2400 DC Output Power Connections If the 93ACC0084 Air Cleaning System is used make sure to power it through the F51 protected block DC Outputs 4...

Страница 14: ...d reading station application The power supply unit is connected to the camera illuminators according to the following diagram power supply side See also the AV7000 Reference Manual or your applicatio...

Страница 15: ...400 power supply by cutting off the cable s male Amphenol connector and connecting the wires to the PWR 2400 according to the table below CVL 2389 Cable to AI7000 Wire Color Meaning White GND 0 V Gree...

Страница 16: ...rotection For primary wiring use a 3 conductor cable between 4 mm2 10 mm2 11 AWG 7 AWG for every conductor Choose the overall cable diameter and UL Listed conduits accordingly The AC input cable must...

Страница 17: ...an it with compressed air or replace it with new filter material The filter type material to use is Class G3 according to norm EN 779 3 Reinsert the clean filter and close the filter grill 6 2 COOLING...

Страница 18: ...20 A for each power module 22 A up to 40 C ambient temp for each power module ENVIRONMENTAL FEATURES Operating Temperature 0 to 50 C 32 to 122 F Storage Temperature 20 to 70 C 4 to 158 F Humidity 5 9...