Grounding Concepts
MX-E Series Hardware Guide
Datalogic S.r.l.
18
Grounding Concepts
Functional ground is a low impedance current path between electrical circuits and ground. It is used, for example, to
improve immunity to disturbances, but is not a protective measure. Grounding deflects disturbances, but does not neces-
sarily provide protection against electric shock.
The functional ground on the processor has two connections:
•
Supply voltage GND terminal
•
Grounding connection on the processor back panel
To guarantee a good functional ground:
•
Connect the processor to the central grounding point in the control cabinet using the shortest route possible.
•
Use a cable with a minimum cross section of 2.5 mm² per connection. If a cable with wire tip sleeves is connected
to the supplied power plug, then a cable with maximum 1.5 mm² per connection is possible.
•
Use shielded cable for all data connections.
Содержание E1 Series
Страница 1: ...MX E Series Hardware Guide for Processor and Cameras Revision Date July 19 2018 ...
Страница 4: ......
Страница 18: ...Before You Call MX E Series Hardware Guide Datalogic S r l 12 ...
Страница 28: ...Battery MX E Series Hardware Guide Datalogic S r l 22 ...
Страница 44: ...M2xx and M3xx Camera Connection MX E Series Hardware Guide Datalogic S r l 38 M2xxandM3xxTerminalConnections ...
Страница 56: ...JAI Cameras MX E Series Hardware Guide Datalogic S r l 50 661 0402TerminalBlockDimensions ...
Страница 58: ...JAI Cameras MX E Series Hardware Guide Datalogic S r l 52 JAITerminalConnections sinking ...
Страница 64: ...Basler Cameras MX E Series Hardware Guide Datalogic S r l 58 TerminalConnections ...
Страница 116: ...M1xx and E1xx MX E Series Hardware Guide Datalogic S r l 110 ...
Страница 120: ...Index MX E Series Hardware Guide Datalogic S r l iv ...